Chapter 1. Installation
1.7.5h Wiring the MODBUS Option Card
The MODBUS option card uses the RS485 standard for MODBUS communication. The MODBUS card must be
installed in Slot 2. The RS485 standard allows up to 32 nodes (drivers and receivers) on one multidrop network, at
distances up to 4,000 ft (1,200 m). GE recommends using 24-gauge (24 AWG) twisted-pair wire with a characteristic
impedance of 120 ohms and 120-ohm termination at each end of the communications line.
Note:
The MODBUS option card provides its own RS485 connections. Thus, the meter can have its serial port
configured as RS232 and still provide RS485 MODBUS signals.
IMPORTANT:
Because the MODBUS option card uses pins 1 and 2 on terminal block
J2
, only those option cards that do
not use these pins may be installed in
Slot 1
, while a MODBUS card is installed in
Slot 2
. Specifically,
only the option cards designated as “OI” and “OR” in Figure 11 on page 26 are compatible with the
MODBUS option card.
To link the XGM868i to the control system (refer to Figure 7):
1.
Connect the MODBUS – wire to pin
#2
, the inverting or negative connection.
2.
Connect the wire to pin
#1
, the non-inverting or positive connection.
3.
Pin
#3
has no connection.
.
Figure 7: The RS485 MODBUS Terminal Block Connector
N/C
MODBUS –
Summary of Contents for DigitalFlow XGM868i
Page 2: ......
Page 4: ...ii no content intended for this page ...
Page 30: ...Chapter 1 Installation 22 DigitalFlow XGM868i Startup Guide no content intended for this page ...
Page 84: ...Warranty 76 DigitalFlow XGM868i Startup Guide no content intended for this page ...
Page 86: ......
Page 88: ......
Page 90: ......
Page 91: ......