Installation
Guide
SG Series
10, 20, 30 & 40 kVA
Openings for input and output cable connections
SG
T50
00_
010
-02
0_U
PS
vie
w t
op_
01U
S
31.
50"
800
mm
9.0
6"
1.58"
40mm
230
mm
9.0
6"
70mm
2.76"
26.78"
680mm
230
mm
Utility input
Output Load
Battery
Fig. 3.4.1-2 Opening on top of the cabinet for input and
cables of
SG
Series
10 and 20 kVA
SG
T50
00_
030
-04
0_U
PS
vie
w to
p_0
1US
31.
50"
800
mm
13.7
8"
1.58"
40mm 110m
m
4.3
3"
70mm
2.76"
26.78"
680mm
350
mm
Utility input
Output Load
Battery
Fig. 3.4.1-3 Opening on top of the cabinet for input and
cables of
SG
Series
30 and 40 kVA
SG
T50
00_
030
-04
0_U
PS
view
bo
ttom
_01
US
26.78"
680mm
7.0
9"
180
mm
70mm
2.76"
50mm
1.97"
7.8
8"
200
mm
31.
50"
800
mm
Utility input
Output Load
Fig. 3.4.1-4 Opening on the bottom of the cabinet for input and
output cables
SG
Series
10, 20, 30 and 40 kVA
SG Series
openings are provided on the
top and the bottom of the UPS for the
connection of input and output cables.
Pay attention to the position of these
openings, when choosing the placement
of the UPS.
These openings are covered with a
protective plate.
Positioning of the UPS cabinet
SG Series
is equipped with wheels for easy
placement of the UPS.
To make the UPS movable on wheels, the
bolts on each leg of the cabinet have to be
turned counter-clockwise, until they are free
from the floor and thus the cabinet supported
on wheels.
After having positioned the UPS at its final
location, the cabinet has to be secured by
rotating the bolts on each leg clockwise, but
the wheels must still touch the floor.
To lower
To lift
Fig. 3.4.1-4 Bolts for the regulation of the cabinet
The UPS cabinet is free
standing and normally does
not require to be bolted to the
floor.
The UPS cabinet can be fixed
however to the floor by bolting
it with the supporting blocks to
the floor.
The supporting blocks can be
used in different positions (0° -
360°)
These supporting blocks are
part of the shipping package.
See
Fig. 3.4.1-5
.
SGT
5000_010-020_U
PS f
ix
ing_01
0 - 360°
Fig. 3.4.1-5 Fixing of the UPS cabinet on the floor