GE
Energy
D400 Substation Data Manager User's Manual
81
7.2
Replacing the Battery
The lithium battery maintains power to the D400's built-in Real-Time Clock and NVRAM if
there is a power disconnect. The D400 is supplied with a 1/2AA 3.6 V 0.9 Ah Lithium
battery that you must insert on the D400 main board when the D400 is installed. To
ensure the battery is good, it is recommended you replace the battery every five years.
You can access the battery compartment by removing the D400 main module from the
chassis. The battery holder
BT1
is located near the front corner of the board, behind the
two rows of Serial Port Status LEDs.
D400 Battery Location
BT1