GE Grid Solutions
D20/D200 Technical Overview
GE Information
PRPI-019-3.00-10
63
Item
Description
Frequency Response
50/60 Hz filtered, 1300 Hz unfiltered
Sample Rate
64 samples per cycle
DC Analog Input
One DC differential analog input
Current Input
One of: + 1, + 5, + 10, + 20 mA
Input Burden
> 10 M voltage input, 5 K to 250 K current input (1 to 20 mA)
Overload
+ 30 VDC (normal mode), 200 VDC (common mode)
Accuracy
+ 0.05% full scale voltage input, + 0.1% full scale current input
Resolution
12 bit plus sign (minimum)
CMRR
90 dB @ 50/60 Hz, NMRR: 60 dB @ 50/60 Hz
Dynamic Range
125% full scale
References
+ 90% full scale zero
Conversion Time
16.7 ms (60 Hz), 20.0 ms (50 Hz)
Temperature Coefficient
+ 15 ppm
o
C voltage input, + 30 ppm
o
C current input
Sample Rate
64 samples per cycle
D.20 Link Ports
2
Maintenance Port
9600 baud, RS-232
Power Requirements
•
40 – 150 VDC, 5 W typical
•
20 – 60 VDC, 8 W
2.4.11.1 D20AC Options
The following D20AC WESDAC and WESTERM options are currently available:
Table 19 D20AC Options
D20AC Option
Description
WESDAC D20AC (40-150V, 511-0104)
Standard version of the AC analog input peripheral logic panel,
supporting up to six 50/60 Hz AC voltage inputs, and up to nine
50/60 Hz AC current inputs. The 511-0104 requires a power source
between 40 and 150 VDC.
WESDAC D20AC (20-60V, 511-0106)
Standard version of the AC analog input peripheral logic panel,
supporting up to six 50/60 Hz AC voltage inputs, and up to nine
50/60 Hz AC current inputs. The 511-0106 requires a power source
between 20 and 60 VDC.
WESTERM D20ACL 3VT/3CT (517-0380)
Termination panel for the D20AC, supporting three AC voltage
inputs and three AC current inputs, which connect through a barrier
terminal strip.
WESTERM D20ACL 3VT/6CT (517-0381)
Termination panel for the D20AC, supporting three AC voltage
inputs and six AC current inputs, which connect through a barrier
terminal strip.
WESTERM D20ACL 3VT/9CT (517-0382)
Termination panel for the D20AC, supporting three AC voltage
inputs and nine AC current inputs, which connect through a barrier
terminal strip.