CB Watch 3 User Manual
v6.3 - May 2019
Page 75 of 100
Related additional sensors
Additional information specific to pneumatic/hydraulic stored energy systems are often
requested, for example:
-
AC supply voltage to the pump
-
Pressure in pneumatic/hydraulic storage tank
This information can be monitored using sensors connected to the generic analogue
channel inputs. Values can be displayed in the HMI and alarms can be set. Please refer to
section 11 for more details.
The interesting feature is that the additional sensors relating to the pump operation can
be grouped on the pump HMI page for ease of viewing. This is done by selecting which of
the generic channels (1 to 4) are relevant to display in the pump page:
HMI: Measurement / Settings / Pump
Figure 126
–
Display of generic channels
As an example, if we connect the sensors that give us the above-mentioned information
to generic channels 2 and 3 and we select these 2 channels to be displayed as part of the
pump data, then we would see the following information in the HMI:
HMI: Measurements / Pump
Figure 127
–
Generic channel display
The description and the units associated with the generic channels are configurable. See
Section 11 for more details.
These selected generic values can also be stored in the “pump” COMTRADE file. See
Section 11 for more details.
Note that when generic channels are selected to appear in the “Measurements/pump”
page of the HMI, they no longer appear in the “Measurements/Sensors” page of the HMI.