Arize
®
Factor
Installation Guide
7
Connect the output of the driver to the first light bar using the 30”
interconnection cable. The output of first light bar (6” cable) must be connected to
the 30” cable of the 2nd lightbar, and so on.
• For ML900, only 2 lightbars should be connected as shown.
• For ML300, a minimum of 4, and a maximum of 6 light bars can be connected.
Connecting less than 4 ML300 light bars may damage the product.
• Connect the shorting cap to the last 6” lightbar cable, as shown, or else the array will
not light. The shorting cap must be secured such that it does not touch the light bar.
Shorting Cap Installation
ML900 Electrical Connection: 2 Lightbars only
ML 300 Electrical connection: 4, 5, or 6 Lightbars only
For all configurations greater than 5 bars, only use 3ft or 6ft extension cable (GECA30A14-AA03B or
GECA30A14-AA06B interconnection cables) in conjunction with LED Drivers without NEMA plugs
(GEPSC210-600D-ADGNA-D1XA1 and GEPSC210-600G-AGJNA-D1XA1).
600W
Driver
Lightbar 1
Interconnection cable
Lightbar 2
600W
Driver
Lightbar 1
Lightbar 3
Lightbar 2
Lightbar 4
Lightbar 5
Lightbar 6
ML300
ML900
RISK OF SAFETY AND PRODUCT DAMAGE. DO NOT MAKE OR BREAK
ELECTRICAL CONNECTION WHILE POWER IS APPLIED.
Shorting Cap
9
1
1
1
1
1
1
1
1
2
2
Shorting Cap
9
Shorting Cap
9
3