FP400 Series

 

Conventional microprocessor 
controlled fire detection and 
alarm panels 

User Guide 

 

 

Version 2.3 / June 2004 

Summary of Contents for ARITECH FP400 Series

Page 1: ...FP400 Series Conventional microprocessor controlled fire detection and alarm panels User Guide Version 2 3 June 2004 ...

Page 2: ...gix brand http www geindustrial com ge interlogix emea 2004 GE Interlogix B V All rights reserved GE Interlogix B V grants the right to reprint this manual for internal use only GE Interlogix B V reserves the right to change information without notice ...

Page 3: ...ide 3 TABLE OF CONTENTS 1 User Guide 4 1 1 Description of control panel 4 2 What to do in case of a fire or fault 9 3 Maintenance 10 3 1 System maintenance 10 3 2 Battery maintenance 10 3 3 Cleaning 10 4 Troubleshooting 11 ...

Page 4: ...4 FP400 Series User Guide 1 USER GUIDE 1 1 Description of control panel Figure 1 FP416 Front Panel Figure 2 FP404 Front Panel ...

Page 5: ...shing yellow LED indicates a fire system fault 6 Disabled A zone or sounder has been disabled 7 Maintenance For installations using Clean Me enabled detectors only A yellow LED indicates detector maintenance is required The detector zone is displayed when the Silence Buzzer key is pressed for more than one second This feature is only available in standby mode 8 Sounder Delay A sounder delay has be...

Page 6: ... activates the corresponding LED C Reset Restarts the system Any fault or alarm that has not been resolved will be highlighted again D Sounder ON Activates the sounder outputs If a delay is programmed it may be disabled by pressing this button from level 1 E Sounders silence Disable Stops the sounder outputs if they are activated and activates the corresponding LED If the sounders are not active t...

Page 7: ...not recommended to reset the system until the location and resolution of the cause of the alarm has been established It is required that the control panel key is in the ON position in order to be able to reset the panel Fault When the fire panel detects a fault its type and location will be shown as LED indicators of general fault flashing of zone fault flashing power fault constant ON or sounder ...

Page 8: ...et the system to check the detector or zone again without having to walk to the fire panel This is reported in the following way LED indicators the general Test LED is steady ON as well as the Fault LED of the zone in test There is no acoustic signal If someone wishes to activate the sounders during the test mode it will not have any programmed delay Out of order The fire panel enters into an out ...

Page 9: ...ry important to keep calm regardless the acoustic signal so the right decisions may be taken KEYPAD ACCESS 2 Remember To be able to operate the fire panel keypad it is required to place the key in the ON position PRESS THE SILENCE BUZZER BUTTON 3 The user may press the Silence Buzzer button in order to silence the internal buzzer This will help to think about what to do under better conditions Sou...

Page 10: ...perts in fire systems This check must test one device per zone supervising the activation of the corresponding outputs verification of batteries and their load voltage Annual Verification All the system devices must be checked annually Recommended Keep a register book for noting down all system incidents such as fire alarms faults modifications to the installation etc 3 2 Battery maintenance The b...

Page 11: ...ct the supplier The general fault and disconnection LED indicators are on and the buzzer is sounding intermittently The panel has no power supply from the mains and the battery is below 22 V minimum working voltage Disconnect the battery and the power supply until the mains voltage or charged batteries can be supplied The general fault and zone failure LED indicators are on flashing and the buzzer...