background image

8

Installing the water heater.

Customer Service

T

roubleshooting Tips

Care and Cleaning

Operating Instructions

Installation Instructions

Safety Instructions

Combustion and Ventilation Air

Proper operation of the water heater
requires air for combustion and
ventilation. Provisions for combustion
and ventilation air must comply with
referenced codes and standards.

When installed in a closet, DO NOT
block or obstruct any of the combustion
air inlet openings located around the
perimeter of the water heater. A
minimum of 1” is required between
these combustion air inlet openings and
any obstruction.

NOTICE:

If the water heater is installed

in an unconfined space within a building
of conventional frame, masonry or metal
construction, infiltration air is normally
adequate for proper combustion and
ventilation. If the water heater is installed
in a confined space, provisions for
combustion and ventilation air must be
made.

A confined space is one having a volume of
less than 50 cubic feet per 1000 Btuh of
the aggregate input of all appliances within
that space. 

The air must be supplied through two
permanent openings of equal area. 
One is to be located within 12” above 
the floor and the other is to be located
within 12” from the ceiling.

The minimum net free area of each opening
must not be less than one square inch per
1000 Btuh of the total input rating of all

the appliances in the enclosure (but not
less than 100 square inches), if each
opening communicates with other
unconfined areas inside the building.

Buildings of unusually tight construction
shall have the combustion and ventilation
air supplied from outdoors, or a freely
ventilated attic or crawl space.

If air is supplied from outdoors, directly 
or through vertical ducts, there must be
two openings located as specified above
and each must have a minimum net free
area of not less than one square inch per
4000 Btuh of the total input rating of 
all the appliances in the enclosure.

If horizontal ducts are used to
communicate with the outdoors, each
opening must have a minimum net free
area of not less than one square inch per
2000 Btuh of the total input rating of all
the appliances in the enclosure. If ducts
are used, the minimum dimensions of
rectangular air ducts shall not be 
less than 3”.

NOTICE:

If the duct openings which

supply combustion and ventilation air
are to be covered with a protective
screen or grill, the net free area
(openings in the material) of the
covering material must be used in
determining the size of the openings.
Protective screening for the openings
MUST NOT be smaller then 1/4” mesh to
prevent clogging by lint or other debris.

Corrosive Atmospheres

The air in beauty shops, dry cleaning
establishments, photo processing labs,
and storage areas for liquid and powdered
bleaches or swimming pool chemicals often
contain such halogenated hydrocarbons.

An air supply containing halogenated
hydrocarbons may be safe to breathe, 
but when it passes through a gas flame
corrosive elements are released that 
will shorten the life of any gas burning
appliance.

Propellants from common spray cans 
or gas leaks from A/C and refrigeration
equipment are highly corrosive after
passing through a flame.

The water heater warranty is voided when
failure of the heater is due to operation in
a corrosive atmosphere.

NOTICE: The water heater
should not be installed
near an air supply
containing halogenated
hydrocarbons. 

Inspect Shipment

Inspect the water heater for possible damage. Check the markings on the rating plate of
the water heater to be certain the type of gas supplied corresponds to the water
heater requirements.

Summary of Contents for AP13204-4

Page 1: ...ition System The purpose of this manual is twofold one to provide the installer with basic directions and recommendations for the proper installation and adjustment of the water heater and two for the...

Page 2: ...te is needed to obtain service under the warranty IMPORTANT Fill out and return the Consumer Product Registration Card that is in the back of this manual If you do need service you can relax knowing h...

Page 3: ...ate air supply for proper operation Be sure to inspect the vent system for proper installation at initial start up and at least annually thereafter Refer to the Care and Cleaning section of this manua...

Page 4: ...re Dial DANGER Hotter water increases the Potential for Hot Water SCALDS D A N G E R HOT Water temperature over 125 F can cause severe burns instantly or death from scalds Children disabled and elderl...

Page 5: ...federal state and or local laws rules regulations or customs LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level...

Page 6: ...a qualified technician SAFETY PRECAUTIONS IMPORTANT SAFETY INFORMATION READ ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk o...

Page 7: ...not allow the water heater to ignite until examined by a Qualified Service Technician The water heater must be located so it is not subject to physical damage for example by moving vehicles area flood...

Page 8: ...directly or through vertical ducts there must be two openings located as specified above and each must have a minimum net free area of not less than one square inch per 4000 Btuh of the total input r...

Page 9: ...nk is designed with an air cushion built in that compresses as the system pressure increases thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve Ot...

Page 10: ...lve and discharge line The end of the discharge line should not be threaded or concealed and should be protected from freezing No valve of any type restriction or reducer coupling should be installed...

Page 11: ...than 3 8 psi 10 5 w c for natural gas or 1 2 psi 14 w c for LP gas Gas Supply The branch gas supply line to the water heater should be clean 1 2 black steel pipe or other approved gas piping material...

Page 12: ...Blankets Insulation blankets available to the general public for external use on gas water heaters are not necessary The purpose of an insulation blanket is to reduce the standby heat loss encountered...

Page 13: ...the venting system complies with the guidelines found in the Use and Care Manual and National Fuel Gas Code DO contact a Qualified service technician if the pilot or main burner will not stay lit The...

Page 14: ...nt room to service heater Combustible materials such as clothing cleaning materials rags etc clear of the base of the heater Clearances from combustion air inlet openings observed see page 7 Gas Suppl...

Page 15: ...c chemicals such as those used for boiler treatment into this system Tee fitting for horizontal hot water supply lines Hot water supply to house From HOT outlet on water heater From HOT outlet on wate...

Page 16: ...heater be sure to read and follow the instructions on the label pictured below and all other labels on the water heater as well as the warnings printed in this manual Failure to do so can result in u...

Page 17: ...ps to accumulate near water heater Do Not store or use gasoline or other flammable vapors and liquids such as adhesives or paint thinner in vicinity of this or any other appliance If such flammables m...

Page 18: ...ken The hottest temperature water will be at the top of the tank closest to the outlet pipe delivering hot water to the home Stacking can cause this top layer of water to be hotter than the water towa...

Page 19: ...rs of dependable trouble free service It is recommended that a periodic inspection of the gas control thermostat burner relief valve internal flue way and venting system should be made by service pers...

Page 20: ...g shut down period the water heater s operation and controls should be checked by qualified service personnel Make certain the water heater is completely filled again before placing it in operation NO...

Page 21: ...ed by a clogged qualified service technician Gas Cock Knob not See the Lighting The Water Heater section of this correctly positioned manual Pilot does not stay Loose thermocouple The connection at th...

Page 22: ...essary relight using the instructions in the Lighting The Water Heater section of this manual The gas control thermostat See the Water Temperature Setting of The Water may be set too low Heater sectio...

Page 23: ...Safety Instructions Installation Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Customer Service 23 Notes...

Page 24: ...Customer Service Troubleshooting Tips Care and Cleaning Operating Instructions Installation Instructions Safety Instructions 24 Notes...

Page 25: ...Tube The kit provides extra speed clips and tamper resistant screws Not supplied with all models Burner Assembly Kit Heat Trap Nipple Heat Trap Nipple Replacement parts For 30 40 and 50 gallon models...

Page 26: ...Manufacturer s National Service Department at the following address 2600 Gunter Park Drive Montgomery AL 36109 1413 When contacting the manufacturer the following information will be requested Model a...

Page 27: ...Rheem Manufacturing Company Warranty Registration Department P O Box 34070 Louisville KY 40232 4070 Please place in envelope and mail to Cut here Cut here 27...

Page 28: ...rs Miss Street Address City State Date Placed In Use Month Day Year Zip Code Apt Last Name Phone Number _ _ Complete and mail this Consumer Product Ownership Registration today After mailing the regis...

Reviews: