Figure 2: Horn and strobe settings 

 

 

1. 

JP1: Horn signal jumper: Cut to change from temporal to steady 

2. 

JP2: Strobe signal output: Cut to change from 1 flash per second 
(public mode) to temporal (private mode) 

3. 

JP3: Horn sound output: Cut to change from high dB to low dB 

Note:

 

If the strobe is set to temporal (private mode), this device is 

no longer UL 1971 or ULC-S526 Listed or FM Approved but is 
UL 1638 Listed. 

Figure 3: UL 1971 minimum light output (% of rating vs. angle) 

100

95

90

85

80

75

70

65

60

55

50

45

40

35

30

25

20

15

10

5

0

5

10

15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

95

100

0

5

10 15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

-5

-10

-15

-20

-25

-30

-35

-40

-45

-50

-55

-60

-65

-70

-75

-80

-85

-90

1

2

 

1. Angle 
2. 

Percentage of rated output 

Note: Horizontal and vertical outputs have the same pattern 

Wiring 

Figure 4: Wiring Diagram 

1

2

-

+

 

1. 

From NAC output 

2. 

To next NAC output 

Note: Signal polarity is shown in the alarm condition. 

Figure 5: Mounting diagram 

 

 

Table 3: Strobe operating current in RMS (A) 

 

15 cd 

30 cd 

75 cd 

95 cd 

VDC 0.147 

0.190 

0.316 

0.372 

VFWR 0.189 

0.253 

0.417 

0.451 

VDC = Volts direct current, regulated and filtered 
VFWR = Volts full wave rectified 

Operating currents shown above were measured by UL at 16 VDC and 16 
VFWR. 
 

Summary of Contents for ADTGC-HDVM

Page 1: ...ds and Canadian Electrical Code Part 1 Section 32 and CAN ULC S524 Standard for the Installation of Fire Alarm Systems and in accordance with the local authorities having jurisdiction Table 2 Compatible synchronization module models Description Number Auto sync output module SIGA CC1S SIGA MCC1S GSA CC1S GSA MCC1S Genesis signal master remote mount ADTG1M RM MG1M RM EG1M RM XLSG1M RM G1M RM ZG1M R...

Page 2: ... 50 45 40 35 30 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 1 2 1 Angle 2 Percentage of rated output Note Horizontal and vertical outputs have the same pattern Wiring Figure 4 Wiring Diagram 1 2 1 From NAC output 2 To next NAC output Note Signal polarity is sh...

Page 3: ...ak output at regulated 24 VDC set for temporal tone Table 7 Audible directional characteristics vertical pattern Angle 1 Sound output dBA 2 90 Ref 0 Ref 65 and 135 3 55 and 140 6 1 Angles are measured from a perpendicular axis positive angles are up 2 Peak output at regulated 24 VDC set for temporal tone Figure 6 Light output profile 0 20 40 60 80 100 120 140 160 0 5 10 15 20 25 30 35 40 45 50 55 ...

Page 4: ...formation Manufacturer GE Security Inc 8985 Town Center Parkway Bradenton FL 34202 USA Year of manufacture The first two digits of the DATE MFG number located on the product identification label are the year of manufacture UL ULC rating Regulated 24 DC and 24 FWR This device was tested to the regulated 24 DC FWR operating voltage limits of 16 V and 33 V Do not apply 80 and 110 of these values for ...