2 of 4
P/N 3100616 • REV 4.0 • ISS 30SEP09
Figure 2: Horn and strobe settings
1.
JP1: Horn signal jumper: Cut to change from temporal to steady
2.
JP2: Strobe signal output: Cut to change from 1 flash per second
(public mode) to temporal (private mode)
3.
JP3: Horn sound output: Cut to change from high dB to low dB
Note:
If the strobe is set to temporal (private mode), this device is
no longer UL 1971 or ULC-S526 Listed or FM Approved but is
UL 1638 Listed.
Figure 3: UL 1971 minimum light output (% of rating vs. angle)
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
0
5
10 15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
1
2
1. Angle
2.
Percentage of rated output
Note: Horizontal and vertical outputs have the same pattern
Wiring
Figure 4: Wiring Diagram
1
2
-
+
1.
From NAC output
2.
To next NAC output
Note: Signal polarity is shown in the alarm condition.
Figure 5: Mounting diagram
Table 3: Strobe operating current in RMS (A)
15 cd
30 cd
75 cd
95 cd
VDC 0.147
0.190
0.316
0.372
VFWR 0.189
0.253
0.417
0.451
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Operating currents shown above were measured by UL at 16 VDC and 16
VFWR.