Controls and Indicators
Switch
Type
Function
SERVICE
Momentary contact
pushbutton
When pressed, the module’s Neuron chip broadcasts its unique
48-bit Neuron identification code and program identifier to the
L
ON
W
ORKS
network. This function is used to facilitate
installation of the Module in the L
ON
W
ORKS
network.
Indicator
State
Meaning
PWR
Lighted
(Power) +5 VDC primary power is present at the Module logic
circuitry.
OUT MSG
Flashes briefly
(Outbound Message) An update message for a bound NV is sent
by the Module to the L
ON
W
ORKS
network.
Lighted briefly
Powerup sequence in process.
The configuration parameter value file or the NV bindings are
being saved into the flash memory.
Flashes alternately
with IN MSG LED
A powerup error has occurred. For troubleshooting information,
refer to Chapter 5.
Flashes together with
IN MSG LED
L
ON
W
ORKS
wink function implemented. See “Wink Function” in
Chapter 5.
IN MSG
Flashes briefly
(Inbound Message) Flashes briefly (10ms) when an update
message for a bound NV is received by the Module from the
L
ON
W
ORKS
network.
Also lighted briefly during powerup sequence.
Lighted briefly
Powerup sequence in process.
The NV configuration is being saved into the flash memory.
Flashes alternately
with OUT MSG LED
A powerup error has occurred. For troubleshooting information,
refer to Chapter 5.
Flashes together with
OUT MSG LED
L
ON
W
ORKS
wink function implemented. See “Wink Function” in
Chapter 5.
SVC
Not lighted
Normal operation.
Flashing
(Service) The Module is in a L
ON
W
ORKS
unconfigured state. (The
Module NVs and PLC mapping are configured and it is waiting
for configuration from a network management tool.)
Lighted
When SERVICE button is pressed.
Summary of Contents for 90-30 PLC