The Series 90-30 PLC must be configured to recognize the module as a foreign smart module with
the reference map necessary to implement the network interface. The PLC is configured using
Logicmaster Series 90-30/20/Micro software. (For detailed information, see “Configuring a Third-
Party Module” in the Logicmaster™ 90 Series 90™-30/20/Micro Programming Software User’s
Manual (GFK-0466).
To configure the LBIM in the Series 90 PLC:
1
.
Start Logicmaster 90-30/20/Micro software. From the Main menu, select the Configuration
package (F2). The Configuration Software menu will appear.
2
.
From the Configuration menu, press F1 (I/O Configuration). An I/O Configuration Rack
screen is displayed. Use the arrow keys to select the rack and slot in which the LBIM is to be
configured.
3.
To configure a foreign module, press F8 (other). A detail screen for the slot will appear. Press
F3 (frgn). A Software Configuration screen for a Foreign Module will appear.
4
.
Press the E
NTER
key to display the detail screen for the Foreign Module configuration. This is
the point where the reference map for the LBIM is configured.
5
.
Use the arrow keys to move from field to field. To edit the field contents, type in the desired
value or press the T
AB
or S
HIFT
+T
AB
keys to scroll the values.
Parameter
Description
Module ID
A 1, 2, or 3-digit signed integer value (0—256) representing a vendor
module designation. A range of valid vendor module IDs is used to allow
validation.
Reference Data
Enter the starting address and length for each of the %I, %Q, %AI, and
%AQ references. The reference address parameters default to the next
highest reference address. The size parameters default to zero and are
validated to be within the configuration memory limits and the
configured CPU for the respective reference types.