![GE 90.017.102 Instruction Manual Download Page 155](http://html.mh-extra.com/html/ge/90-017-102/90-017-102_instruction-manual_131799155.webp)
A-16
MIB High Impedance Bus Differntial Relay
GEK-106426B
A.5 EVENTS
APPENDIX A
A
The following information is supplied for each event:
NAME
BIT NUMBER
RECORD
INDEX
NUMBER OF
BYTES
FORMAT
Event code
0
0
2
F5
Date & Time
16
1
6
F1
Idiff phase A
64
4
4
F2
Idiff phase B
96
6
4
F2
Idiff phase C
128
8
4
F2
Trip operation by communications
160
10
2
F4
LEDs and latched outputs reset
161
10
2
F4
Reset 86
170
10
2
F4
Protection status (0=out of service, 1=In service)
185
11
2
F4
Output 1
186
11
2
F4
Output 2
187
11
2
F4
Output 3
188
11
2
F4
Output 4
189
11
2
F4
Input 1
190
11
2
F4
Input 2
191
11
2
F4
Settings change inhibition by DI
193
12
2
F4
Trip operation by DI
194
12
2
F4
Settings group change by DI
198
12
2
F4
Oscillo trigger by DI
199
12
2
F4
86 Status
201
12
2
F4
Oscillo trigger by communications
202
12
2
F4
Setting change
205
12
2
F4
EEPROM error
206
12
2
F4
User settings (0 factory default, 1 when the first change
is made to any setting)
207
12
2
F4
Pickup 87 1_A
208
13
2
F4
Pickup 87 1_B
209
13
2
F4
Pickup 87 1_C
210
13
2
F4
Pickup 87 1
211
13
2
F4
Pickup 87 2_A
212
13
2
F4
Pickup 87 2_B
213
13
2
F4
Pickup 87 2_C
214
13
2
F4
Pickup 87 2
215
13
2
F4
General Pickup
223
13
2
F4
87 1 inhibition by DI
227
14
2
F4
87 2 inhibition by DI
231
14
2
F4
General inhibition by DI
239
14
2
F4
Trip 87 1_A
240
15
2
F4
Trip 87 1_B
241
15
2
F4
Trip 87 1_C
242
15
2
F4
Trip 87 1
243
15
2
F4
Trip 87 2_A
244
15
2
F4
Trip 87 2_B
245
15
2
F4
Trip 87 2_C
246
15
2
F4
Trip 87 2
247
15
2
F4
General Trip
256
15
2
F4