8-18
MIB High Impedance Bus Differntial Relay
GEK-106426B
8.16 USER SETTINGS
8 RELAY COMMISSIONING
8
8.16.2.2 DIFFERENTIAL CURRENT UNITS GROUP 2
8.16.2.3 EVENT MASK
ENERVISTA MIIPC
HMI
USER VALUE
RANGE
STEP
GROUP 2 FIRST LEVEL
DIFFERENTIAL
FUNCTION
87 1 FUNCTION GROUP2
F87 1 G2
First Level 87 Enable
87 1 G2 Enable
ENABLE 87 1 G2
Y/N
NA
Permission to Trip First
Level 87
87 1 G2 Trip Enable
TRIP 87 1 G2
Y/N
NA
First Level 87 Tap / Pickup
Value
87 1 G2 Pickup Level
TAP 87 1 G2
0.005-0.04 A
0.01 A
First Level 87 Definite
Time Delay
87 1 G2 Time Delay
TIME 87 1 G2
0 – 600.00 s.
0.01 s.
GROUP 2 SECOND
LEVEL DIFFERENTIAL
FUNCTION
87 2 FUNCTION GROUP2
F87 2 G2
Second Level 87 Enable
87 2 G2 Enable
ENABLE 87 2 G2
Y/N
NA
Permission to Trip Second
Level 87
87 2 G2 Trip Enable
TRIP 87 2 G2
Y/N
NA
Second Level 87 Tap /
Pickup Value
87 2 G2 Pickup Level
TAP 87 2 G2
0.005-0.04 A
0.01 A
Second Level 87 Definite
Time Delay
87 2 G2 Time Delay
TIME 87 2 G2
0 – 600.00 s.
0.01 s.