DE GT Series: User manual rev date 8-11- 04

 

Digital Energy

 

GT Series

g

 

 

 

 

 

1.1  Save these instructions 

 

This manual contains

 

important instructions for the 

Digital Energy™ GT Series-UL

 

UPS that should be followed during installation and maintenance of the UPS and the 
batteries. 

 

Before attempting to install and start up the UPS, carefully read this 
manual. Keep this manual next to the UPS for future references. 
All servicing must be done by qualified personnel. Do not attempt 
to service the UPS unless you have had proper training. 

 

WARNING:

 By opening or removing covers you run the risk of 

exposure to dangerous voltages !

 

 

While every care has been taken to ensure the completeness and accuracy of 
this manual,  GE  accepts no responsibility or liability for any loss or damage 
resulting from the use of the information contained in this document. 
This document shall not be  copied nor reproduced without the permission of 
GE. Due to technical improvements, some of the information contained in 
this manual may be changed without notice. 

 

1.2  General 

 

 

CAUTION

: RISK OF ELECTRIC SHOCK.

  

  The UPS has an internal battery supply, with a nominal voltage of (UPS rating / 

voltage): 1kVA / 36Vdc,  1.5kVA / 72Vdc, 2kVA / 72Vdc,  3kVA / 72Vdc. 

  The appliance outlets may be electrically live, even when the UPS is disconnected 

from the utility supply. Dangerous voltages may be present during battery operation. 

  Do not open the unit, there are no user serviceable parts inside. 

  The batteries must be disconnected during maintenance or service work. 

  The UPS contains potentially hazardous voltages. 

 

1.3  Installation  

 

  The unit should be installed by service personnel. 

  To reduce the risk of electric shock, install this UPS in a temperature and humidity 

controlled indoor area free of conductive contaminants.  

  Ambient temperature must not exceed 40°C (104°F). Optimal battery lifetime is 

obtained if the ambient temperature does not exceed 30

°

C (86

°

F). 

  It is important that the unit has adequate ventilation. Maintain air movement around 

and through the unit. Do not block the air vents. 

  Avoid placing the unit in direct sunlight or near heat sources. 

  The UPS should only be powered from a 2-pole 3-wire grounded wall outlet. This 

outlet must be easily accessible and located near the UPS.  

  Do not use extension cords when connecting the UPS to the utility power supply.  

  The AC output of  the UPS needs a disconnecting switch such as a breaker which 

has to be provided by others. 

  The overcurrent protection for the output AC circuit has to be provided by others. All 

of our UPS have an electronic protection of AC output short circuit. 

  Avoid spilling liquids on or dropping any foreign object into the UPS. 

  Do not plug a laser printer or household appliances such as electric heaters or 

vacuum cleaners into the UPS. The UPS output is intended to be used only for 
electronic loads such as computers and telecommunications equipment. 

  Upon installation, it should be ensured that the sum of the leakage currents of the 

UPS and the connected loads does not exceed 3.5mA.  

  The unit should be operated by properly trained personnel. 

1   -  Important Safety Instructions

 

Summary of Contents for 1000-1500-2000-3000 VA

Page 1: ...upply 1000 1500 2000 3000 VA UL version Manufactured by GE Consumer Industrial General Electric Company Telephone 903 640 7900 2501 Pecan Street Fax 903 640 0535 Bonham TX Website www geindustrial com Technology for the Digital World ver 1 2 US GT Series UPS TM ...

Page 2: ...e power failures Please keep this manual in a safe place for future reference and carefully read the important safety instructions in chapter 1 before installation and start up of the UPS 2004 by GE Consumer Industrial All rights reserved Reproduction in whole or in parts without the prior written consent of GE Consumer Industrial is prohibited The illustrations and plans describing the equipment ...

Page 3: ...0 3 1 Operation Panel 3 2 Start up 3 2 1 Start up utility power available 3 2 2 Start up utility power not available cold start or battery start 3 3 Use Normal Operation 3 3 1 Normal operation conditions 3 3 2 Normal operation indications 3 3 3 UPS self test 3 3 4 Silencing the buzzer 3 3 5 Switching off 3 4 Use Abnormal Conditions 3 4 1 On battery 3 4 2 Battery low 3 4 3 Overload 3 4 4 Bypass ope...

Page 4: ... The batteries must be disconnected during maintenance or service work The UPS contains potentially hazardous voltages 1 3 Installation The unit should be installed by service personnel To reduce the risk of electric shock install this UPS in a temperature and humidity controlled indoor area free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Optimal battery lifetime is ...

Page 5: ...to connecting or disconnecting battery terminals Determine if the battery is inadvertently grounded If inadvertently grounded remove source of ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance applicable to UPS and external battery supply not having a grounde...

Page 6: ...ed interface cables when connecting to computer or peripheral devices Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate this equipment This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must acce...

Page 7: ...put currents 7 Communication interface RS232 dry contact Allows communi cation between computer and UPS See chapter 4 for more detailed information 3 Output receptacles To connect critical load to the UPS 4 Output circuit breaker Protects the UPS from damage caused by output overload 8 TVSS Transient Voltage Surge Suppressor RJ 45 RJ 11 To prevent damage caused by surges noise and spikes traveling...

Page 8: ... 2 2 4 2 Connecting an external battery pack 1 Before installation check whether the nominal voltage of battery pack is suitable for the UPS The voltages mentioned on the battery connectors should match 2 Utilize the battery connection cable that came with the battery pack to connect the battery pack to the UPS as shown in fig 2 5 The other connector of the battery pack can be used to connect a se...

Page 9: ...the UPS as shown in fig 2 4 Spread the load ove r the output receptacles as equally as possible CAUTION Do not connect a laser printer to the UPS 2 4 5 Connecting to the utility power supply 1000VA Use a suitable power cord and plug it into the input socket see fig 2 4 1500 2000 3000VA The UPS is equipped with a fixed input power cord 1 Plug the input power cord into a working three wire grounded ...

Page 10: ... sufficient runtime in case of a utility power failure 2 4 6 Checking the site wiring fault LED When the UPS is still in STAND BY mode check the site wiring fault LED If the UPS is plugged into an improperly wired AC utility power outlet this LED flashes as shown in Fig 2 6 The detection of site wiring faults includes a missing ground phase neutral polarity reversal and an overloaded neutral circu...

Page 11: ...150Vac 5 LED On Line The UPS is operating in the normal ON LINE mode 6 LED On Battery The UPS is operating in ON BATTERY back up mode utility power fails and the internal batteries supply the required power until either they are depleted or utility power returns 7 Level bar In ON BATTERY mode shows current battery capacity In ON LINE mode showing current load level 8 Battery LED Level bar shows cu...

Page 12: ...discharges the batteries 3 3 Use Normal Operation 3 3 1 Normal operation conditions the utility power supply is present and within allowable tolerances the load does notexceed the nominal rating of the UPS and the operating temperature is below alarm level the UPS is on 3 3 2 Normal operation indications LEDs Line On Line and the Load LED are on One or more LEDs on the level bar are on the buzze r...

Page 13: ...uzzer beeps with a 2 seconds interval When the utility power returns the UPS will switch back to normal operation In case of a long power failure the UPS will stop operating when the batteries have been depleted see Chapter 8 Battery Back up Time 3 4 2 Battery low The batteries are nearly discharged during battery operation see 3 4 1 The LED On Battery and the Battery Low LED will light and the bu...

Page 14: ... If the UPS functions under overload or over temperature conditions it may not be able to protect the load 3 4 5 Replace battery The batteries are aged and must be replaced as soon as possible to ensure fu ll protection for your equipment The Replace Battery LED lights and the buzzer sends out three beeps every hour until the batteries have been replaced 3 4 6 Short circuit In case of a short circ...

Page 15: ...itoring software For specific information on Digital Energy GTSeries connectivity products please contact your local dealer or Internet http www geindustrial com cwc products famid 46 lang en_US The dry contacts 4 3 and optional SNMP plug in card 4 4 can be connected at the same time However if both are operating simultaneously the remote shutdown facility for the dry contacts will not be availabl...

Page 16: ...CII format Hardware Baudrate 2400 bps Data length 8 bits Stop bit 1 bit Parity none Cabling Standard sub D 9 cable UPS side male PC side female 4 3 Dry Contact Its major functions are some or all of the following 1 to broadcast a warning when the AC utility power fails 2 to save open files before the battery is exhausted 3 to turn off the UPS via computer s Pin Assignment Pin 1 Normally open When ...

Page 17: ...TTP protocol you can use browser Microsoft IE or Netscape Communicator to monitor or configure the UPS Besides the SNMP card supports Telnet and FTP for remote monitoring and firmware upgrading Specifications 1 Auto detecting 10 100M Network speed 2 Supporting protocol TCP IP UDP HTTP ICMP ARP TELNET BOOTP DHCP FTP and SNMPv1 3 Remote firmware upgradeable and configurable 4 Web server built in all...

Page 18: ...6 2 Batteries General The service life of the battery is from 3 to 6 years depending on the operating conditions mainly temperature and number of discharge cycles As a healthy battery is critical to the performance of the UPS it is advised to regularly perform a battery test to ensure failsafe operation see section 3 3 3 When the condition of the battery is critical a replace battery alarm will be...

Page 19: ... has no output UPS over temperature Allow UPS to cool down Utility failure battery depleted Wait until utility power returns Input breaker tripped See above LED Fault lights up buzzer sounds conti nuously Internal UPS failure Contact your dealer or consult www gedigitalenergy com LED Fault flashes Wiring fault L N reversed Have site wiring checked by qualified electrician LED Battery low lights up...

Page 20: ...72V Battery Type Lead acid 12V 7Ah 12V 7Ah 12V 9Ah Back up Time Typical 5mins Battery Recharge Time 4 6 hours after complete discharge to recover 90 Transfer Time Transfer Time zero LED Status On line Bypass On battery Overload Battery Low Fault Battery Replace Battery Level Load Level LED Alarm buzzer DB9 RS232 dry contact Interface SNMP Slot internal Noise At 1 Meter 40dB A 42dB A 45dB A Operati...