background image

FS-9006OM 

– REV K 

 

 

 

 INTRODUCTION 

 

1.1 SPECIFICATIONS 

 

1.1.1 

Flame Tracker™ -RS-FS-9006 

 

Mechanical 

 

Body Mount:

 

AISI316 Stainless Steel 

 

Housing: 

AISI304 Stainless Steel (sealed and Argon filled)

 

Connector 

 

Process: 

3/4” NPT female

 

Electrical: 

MIL-C-38999 Series III size 15 (5 pin)

 

Sensor: 

Silicon Carbide photodiode

 

Window: 

Sapphire

 

 

Operating

 

 

Sensitivity: 

>5 mA @ 1x10

10

 photons/in

2

/sec. @ 310 nm 

Output: 

4 - 20 mA dc, Max < 21 mA 

Response Time: 

<25 milliseconds 

Power Requirements: 

12 - 30 vdc @  100 mA 

Temperature Range 
(ambient): 

 

-40

F to 302

F (-40

C to 150

C) 

455

F (235

C) with specified air cooling 

 

Relative Humidity 

Process Pressure 

Vibration 

100%  Non-Condensing 

400 psig (2.8 Mpa) 

0.0125 inches DA 10 

– 88 Hz 

5 G continuous 88 

– 1200 Hz 

 

Summary of Contents for 07482SOCNL44819P01

Page 1: ...S FS 9006 GE 07482SOCNL44819P01 Operation and Maintenance Manual FS 9006OM Rev K November 2017 www gemeasurement com A trademark of Baker Hughes a GE company LLC 2017 Baker Hughes a GE company All rights reserved Technical content subject to change without notice ...

Page 2: ...NG AS WELL AS WARRANTIES IMPLIED FROM A COURSE OF PERFORMANCE OR COURSE OF DEALING THE MATERIALS IN THIS MANUAL WILL BE ERROR FREE OR THAT THE MATERIALS IN THIS MANUAL WILL BE COMPLETE ACCURATE OR TIMELY NO ADVICE OR INFORMATION OBTAINED BY YOU FROM REUTER STOKES LLC OR THROUGH THE CONTENT AND MATERIAL IN THIS MANUAL SHALL CREATE ANY WARRANTY OF ANY KIND REUTER STOKES LLC DOES NOT MAKE ANY WARRANT...

Page 3: ...94 WRTR L Lombardo REV E DATE 06 25 10 ECN 40293054 WRTR R Martin REV F DATE 04 24 13 ECN 77469075 WRTR J Hashmi REV G DATE 12 18 15 ECN 500000157848 WRTR J Hashmi REV H DATE 02 22 16 ECN 500000204318 WRTR J Hashmi REV J DATE 08 24 17 ECN 500000263564 WRTR J Hashmi REV K DATE 11 03 17 ECN 500000272164 WRTR J Hashmi ...

Page 4: ... Ta 235ºC T2 with cooling coil South Korea KTL hazardous area mark Customs Union hazardous area mark China hazardous area mark Brazil INMETRO hazardous area mark India hazardous area approved Taiwan hazardous area mark These certifications are based on the use of approved interconnecting cables only Currently available approved interconnecting cables are BHGE Reuter Stokes RS E2 0285PXXX and GE 36...

Page 5: ... by wrenching on the body Always use the 1 3 8 inch mounting nut Wrenching on the body may breach the seal Breaching the seal of the sensor will cause loss of the inert fill gas and render the sensor unusable Do not install a sensor that has a cracked window damaged threads or one that has been disassembled Do not install or remove the flame sensor from the sight tube with the cooling coils attach...

Page 6: ...NTERCONNECTING CABLE RS E2 0279PXXX OR 362A1053PXXX 2 1 2 REFERENCE 3 1 3 GENERAL DESCRIPTION 4 2 SENSOR 4 3 INSTALLATION 5 3 1 MECHANICAL 5 3 2 ELECTRICAL 7 3 3 CONNECTOR PINOUT 8 3 4 SENSOR CHECKOUT 8 3 5 CONTROLLER SETUP 8 4 Maintenance 9 4 1 WARNING 9 4 2 CAUTION 9 5 TROUBLESHOOTING 9 5 1 WARNING 9 5 2 CAUTION 9 ...

Page 7: ...es III size 15 5 pin Sensor Silicon Carbide photodiode Window Sapphire Operating Sensitivity 5 mA 1x1010 photons in2 sec 310 nm Output 4 20 mA dc Max 21 mA Response Time 25 milliseconds Power Requirements 12 30 vdc 100 mA Temperature Range ambient 40 F to 302 F 40 C to 150 C 455 F 235 C with specified air cooling Relative Humidity Process Pressure Vibration 100 Non Condensing 400 psig 2 8 Mpa 0 01...

Page 8: ...ge 1 02 mm 19 strand nickel plated copper Insulation Teflon PTFE Shield Jacket 36 gauge 0 127 mm nickel plated copper braid Extruded PFA Armor Stainless steel braid Connector MIL C 38999 series III shell size 15 5 16 pins only 3 pins are used Operating Voltage max 300 vrms Temperature max 482 F 250 C ...

Page 9: ...FS 9006OM REV K 3 1 2 REFERENCE ...

Page 10: ...on a number of GE gas turbine installations 2 SENSOR Figure 1 is a block diagram of the SiC Flame Sensor The sensor has a sapphire window that is transparent to UV light and can withstand the compressor discharge temperature and pressure It has a lens inside that focuses the light on a silicon carbide photodiode in a hermetic package The photodiode is wired to a MOSFET input amplifier The amplifie...

Page 11: ... 1 5 m sec or greater at a temperature of 50 F 10 C or less above outside ambient Under these conditions the sensors will operate at outside ambient temperatures up to 140 F 60 C Air cooling with pressurized air requires the use of Air Cooling Can BHGE Reuter Stokes Part Number RS E2 0259 GE Part Number 07482SOCNL44821P01 The Air Cooing Can is installed as shown in the following drawing The Air Co...

Page 12: ...applied below the 2nd thread If Never Seez is applied to the face of the sight tube upon heating it can fog the window of the Flame Sensor 3 Inspect the window and clean with Isopropanol soaked swab If required install hand tight 3 4 Full turns tighten with a wrench approximately 2 5 turns Tighten further as required to align keys on cable connector with slots in sensor connector 4 Slide cooling c...

Page 13: ...her or to earth ground at any location The inner shields should be individually jumpered through all junction boxes and connected to the proper ground terminal at the Controller The polarity of the cable is red wire is positive and black wire is negative The polarity is shown in the drawings Reverse polarity will not damage the sensor Signal cable from the junction box to the Controller should be ...

Page 14: ... see zero flame intensity signal and with a flashlight to see a positive reading With no light the reading should be 3 7 to 4 1 milliamps while with most flashlights the reading should be above 8 milliamps An LED flashlight may not work for this application Variations in flashlight type strength or battery voltage may cause variations in signal output The flashlight test is intended as a field tes...

Page 15: ...eize compound should be applied to the mounting thread prior to reinstallation of the sensor 5 TROUBLESHOOTING 5 1 WARNING Do not disconnect connector while circuit is energized or live unless area is known to be non hazardous 5 2 CAUTION The operating temperature range of the Flame Sensor is 40 C to 150 C Do not attempt to work on the Flame Sensor or the cable until they have cooled to a safe han...