GE Security Simon XT V2 Installation Manual Download Page 7

There is a 30 second delay. 

4.  When you finish testing the system, call the central 

station to verify that the alarms were received. 

Specifications 

 
Power 

9 VAC, 60 Hz, 25 VA transformer minimum 

Rechargeable battery: 6.0 VDC, 1.2 Ah lead-acid. 
The battery will last 24 hours with no AC and 
specified standby load of 250 mA. Maximum 
battery charging current is 45 mA. With loss of 
AC, panel will continue to operate normally to a 
minimum of 5.1 VDC. 

Radio frequency 

319.5 MHz 

Storage temperature 

-29 to 140ºF (-34 to 60ºC) 

Operating 
temperature 

32 to 120ºF (0 to 49ºC) 

Maximum humidity 

85% relative humidity, noncondensing 

Auxiliary power 

Unregulated 5.3 to 12.3 VDC, with a maximum of 
250 mA 

 

Regulatory information 

UL listed installations 

Some installation may require configurations dictated by 
city/state codes, insurance, or Underwriter’s Laboratories 
(UL). This section describes the various component and 
configuration listings. 

Basic system: 

•  Control panel: Backup battery 6 V 1.2 Ah (34-025) 

(Portalac model # PE6V1.2) 

•  Standard class 2, 9 VAC, 3.34 A power transformer (GE 

Security part 22-153). Alternate transformer for US 
installations: MG Electronics model MGT925, 9 VAC, 25 
VA, (GE Security part 22-155) 

•  Hardwired siren (13-374) 

Household burglary alarm system unit (UL 1023), basic 
system plus the following: 

•  Hardwired magnetic contact (13-068 or 13-071) or 

wireless learn mode door/window sensor (60-670) 

•  Panel piezo beeps set to on 
•  Entry delay set to 45 seconds or less 
•  Exit delay set to 60 seconds or less 
•  RF time-out set to 24 hours 
•  Control panel alarms turned on 
•  Auto arm set to on 
•  Siren timeout set to 5 minutes or more 
•  Trouble beeps set to on 
•  RF jam detect set to on 

•  Hardwired siren supervision set to on 
•  Exit extension set to off 
•  Quick exit set to off 

Household fire warning system (UL 985), basic system plus 
the following: 

•  Wireless smoke sensor 60-848-02-95, TX-6010-01-1 

learned into sensor group 26. 

•  Panel piezo beeps turned on 
•  Control panel alarms set to on 
•  Siren timeout set to 4 minutes or more 
•  Trouble beeps set to on 
•  RF jam detect set to on 
•  Hardwired siren supervision set to on 
•  Smoke supervision set to on 

UL 1023 and 985 24-hour backup: 

•  For 24-hour backup, the total current draw for all 

connected devices is limited to 240 mA (during normal 
standby conditions) using a 1.2 AH battery. 

UL 1635 digital alarm communicator system (same as UL 
1023 and 985) plus the following settings are in addition to 
UL 1023 and 985 and are required only if the system is set 
up for central station reporting: 

•  Phone mod 1 set to 0 or 1 
•  Automatic phone test set to 001 
•  RF timeout set to 4 hours 
•  AC power failure report set to on 
•  CPU low battery report set to on 
•  Fail to communicate set to on 
•  Entry delay plus the dialer delay must not exceed 60 

seconds 

SIA system requirements 

SIA system requirements are the same as those described 
for a UL-listed basic system, plus if multiple annunciations 
are required, use hardwired siren 13-046. 

Note: 

For UL 1635 installations, entry delay plus dialer abort 

delay must not exceed 60 seconds. 

Table 8 below describes programming requirements to 
meet ANSI-SIA CP-01. 

Table 8: SIA setting requirements   

Function Default 

setting 

Required 

setting 

Entry delay 

30 seconds 

30 to 240 seconds 

Exit delay 

60 seconds 

45 to 240 seconds 

Dialer delay 

30 seconds 

15 to 45 seconds 

Auto arm 

On 

On 

Unvacated premises 

On 

On 

Simon XT V2 Installation Guide 

Summary of Contents for Simon XT V2

Page 1: ... intrusion protection Table 1 below describes the recommended sensor groups Table 1 Recommended sensor groups Device Recommended sensor group Indoor motion sensor 17 a Outdoor motion sensor 25 chime only group b Entry exit door 10 Interior door 14 Window sensor 13 Smoke sensor 26 c Key fob 01 ELM key fob 01 Remote handheld touchpad 01 CO alarm 34 b Freeze sensor 29 b Water sensor 38 b Personal hel...

Page 2: ...nect hardwired reed switches normally closed loop only to HW1 I O if not being used for a hardwired siren an or HW2 in terminal 3 Connect only normally closed NC reed switches to HW1 I O and or HW2 in Other types of hardwired detectors should not be used The total resistance of the wired loop must not exceed 3 ohms This allows you to use up to 200 ft 61 m of two conductor 22 gauge stranded wire Co...

Page 3: ... end of the red battery lead to the red battery tab 2 Connect the lug end of the black battery lead to the black battery tab 3 Align the red battery terminal with the right end of the terminal strip The logo and specification information should be readable 4 Insert the front end of the battery under the forward battery compartment latch 5 Push forward and rotate the battery downward until it seats...

Page 4: ...vity if no access code has been entered yet After an access code has been entered to access a code protected area of the system menu the timeout is four minutes Menu navigation Each menu contains a list of options and or submenus Press the scroll buttons to navigate up and down the list of options and submenus in that menu Pressing OK after navigating to an option selects that option for editing a...

Page 5: ...panel memory The panel recognizes a sensor when you press a sensor program button press and release a tamper switch press a sensor test button or put a sensor into alarm Table 6 below describes the programming method for each device Note If you are installing a sensor on a gun case jewelry box or a similar case and the sensor is active in level one you must subdisarm to avoid putting the panel int...

Page 6: ...en all sensors have been tested the display shows SN Test Complete Press Status 3 Press Status The display shows Sensor Test OK If you press Status and the panel has not heard from all sensors the display shows SN Test Fail or Aborted Table 7 Sensor tripping instructions Sensor Do this Door window Open the secured door or window Freeze Remove the sensor cover Apply ice in a plastic bag to the sens...

Page 7: ... set to 5 minutes or more Trouble beeps set to on RF jam detect set to on Hardwired siren supervision set to on Exit extension set to off Quick exit set to off Household fire warning system UL 985 basic system plus the following Wireless smoke sensor 60 848 02 95 TX 6010 01 1 learned into sensor group 26 Panel piezo beeps turned on Control panel alarms set to on Siren timeout set to 4 minutes or m...

Page 8: ...allations Canadian standards CSA certified accessories Standard Class 2 9 VAC 3 34 A power transformer GE Security model 22 153 CN Residential burglary alarm system unit ORD C1023 1974 basic system as described for UL 1023 listed installations plus Hardwired magnetic contact 13 068 or 13 071 or wireless learn mode door window sensor 60 670 Siren timeout set to six minutes or more Residential fire ...

Reviews: