Z
ONE CONFIGURATIONS AND PARTITION SELECTION
Zones can be assigned to different zone configurations (zone types). The programming for all
zone information is performed in the control panel. For instructions on accessing and
programming the NX-8, as well as changing the characteristics of a configuration group, refer
to the NX-8 installation manual.
T
ERMINAL DESCRIPTION
TERMINAL
DESCRIPTION
POS
Connect to the KP POS terminal of the control panel. Current draw is 30 mA.
COM
Connect to the KP COM terminal of the control panel.
DATA
Connect to the KP DATA terminal of the control panel (see the wiring diagram for wire
specifications).
TAM
Connect as shown below. If not used, connect to a COM terminal.
AUX
Can be used to power devices directly from the NX-216Z8. Power is coming from the control
panel, therefore the current draw of these devices must be added to the total current draw of the
NX-216Z8. This output is current limited to 100 mA.
Z9
Connect to one side of zone 9 loop. Connect the other side to COM terminal. Open or short causes
alarm (see wiring diagram for examples).
COM
Common (-) terminal for zones 9 & 10.
Z10
Connect to one side of zone 10 loop. Connect the other side to COM terminal. Open or short
causes alarm (see the wiring diagram for examples).
Z11-Z16
Connect as described for Z9 & Z10.
Z17-Z24 Not
used
NX-216Z8 Installation manual
Page 8