11. KEYBOARD AND DISPLAY
11-6
DTP-B Digital Transformer Protection
GEK-106243E
Level 1
Level 2
Level 3
Presentation
Valid Range
Disabled
87 TRIP
Allowing or not the function trip
Allowed / Not
allowed
DIFFERENT.
FUNCTION
SENSITIVITY Sensitivity
of
the protection
0.2 - 0.4 x It
%
RESTR
CHANGE
Inflexion point between the two
slopes of the protection
0 - 10 x It
% RESTRAINT K1
Percentange restraint of the first
slope
15% - 100%
% RESTRAINT K2
Percentage restraint of the second
slope
15% - 100%
2
nd
HARM RESTR
Second harmonic restraint
12% - 100%
5
th
HARM RESTR
Fifth harmonic restraint
12% - 100%
87B TAP
Pickup value for the 87B unit
4 - 12 x It