13-98
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
44102
0x1005 Events
0
1
1
FC126
1
1
Y Y Y Y
44103
0x1006 Targets
0
2
1
FC101
2
1
Y Y Y Y
Analog Input 2
44108
0x100B Function
0
3
1
FC386
0
1
Y Y Y Y
44109
0x100C Name
0
65535
1
F60_26 AnIp 2
13
Y Y Y Y
44122
0x1019 Unit
0
65535
1
F60_6
units
3
Y Y Y Y
44125
0x101C Range
0
4
1
FC274
0
1
Y Y Y Y
44126
0x101D Min Value
-500000
500000
1
User-
Defined
@
Modbus
44122
F30
0
2
Y Y Y Y
44128
0x101F Max Value
-500000
500000
1
User-
Defined
@
Modbus
44122
F30
0
2
Y Y Y Y
44130
0x1021 Trip Function
0
4
1
FC100D 0
1
Y Y Y Y
44131
0x1022 Trip Type
0
1
1
FC275
0
1
Y Y Y Y
44132
0x1023 Trip Pickup
-500000
500000
1
User-
Defined
@
Modbus
44122
F30
20
2
Y Y Y Y
44134
0x1025 Trip Dropout Ratio
2
20
1
%
F0
5
1
Y Y Y Y
44135
0x1026 Trip Pickup Delay
0
600
1
s
F0
2
1
Y Y Y Y
44136
0x1027 Trip Dropout Delay
0
600
1
s
F0
0
1
Y Y Y Y
44137
0x1028 Trip Output Relay
0
0xFFFFFFFF
1
FC198D 0
2
Y Y Y Y
44139
0x102A Alarm Function
0
3
1
FC100E 0
1
Y Y Y Y
44140
0x102B Alarm Type
0
1
1
FC275
0
1
Y Y Y Y
44141
0x102C Alarm Pickup
-500000
500000
1
User-
Defined
@
Modbus
44122
F30
10
2
Y Y Y Y
44143
0x102E Alarm Dropout Ratio
2
20
1
%
F0
5
1
Y Y Y Y
44144
0x102F Alarm Pickup Delay
0
600
1
s
F0
2
1
Y Y Y Y
44145
0x1030 Alarm Dropout Delay
0
600
1
s
F0
0
1
Y Y Y Y
44146
0x1031 Alarm Output Relay
0
0xFFFFFFFF
1
FC198C 0
2
Y Y Y Y
44148
0x1033 Block
0
0xC6CD00
1
FC142
0
2
Y Y Y Y
44150
0x1035 Events
0
1
1
FC126
1
1
Y Y Y Y
44151
0x1036 Targets
0
2
1
FC101
2
1
Y Y Y Y
Analog Input 3
44156
0x103B Function
0
3
1
FC386
0
1
Y Y Y Y
44157
0x103C Name
0
65535
1
F60_26 AnIp 3
13
Y Y Y Y
44170
0x1049 Unit
0
65535
1
F60_6
units
3
Y Y Y Y
44173
0x104C Range
0
4
1
FC274
0
1
Y Y Y Y
44174
0x104D Min Value
-500000
500000
1
User-
Defined
@
Modbus
44170
F30
0
2
Y Y Y Y
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5