CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–95
5.13.3 Analog Input Diff 1-2
PATH: SETTINGS
ZV
S12 ANALOG I/O
ZV
ANALOG INPUT DIFF 1–2
Note
This settings menu is seen only if Analog Inputs 1 and 2 are enabled. The
ANALOG IN DIFF 1-
2 TRIP LEVEL
and
ANALOG IN DIFF 1-2 ALARM LEVEL
settings are shown units of “%” if the
ANALOG IN DIFF 1-2 COMPARISON
is “%Diff” or in units defined by the
ANALOG INPUT 1 UNITS
settings if
ANALOG IN DIFF 1-2 COMPARISON
is “Abs Diff”.
This feature compares two analog inputs and activate alarms or trips based on their
difference, which can be an absolute difference in units or a percentage difference. The
second analog input (2 for 1-2) is used as the reference value for percentage calculations.
The comparison logic can also be selected as one input greater than the other (“1>2”) or
vice versa (“2>1”) or as absolute difference (“1<>2”). The compared analog inputs must be
programmed with the same units type prior to programming this feature.
ANALOG
INPUT
[
Z
]
ANALOG IN DIFF 1-
2:
Range: Disabled, Enabled
MESSAGE
ANALOG IN DIFF 1-
2
Range: 12 alphanumeric characters
MESSAGE
ANALOG IN DIFF 1-
2
Range: % Diff, Abs. Diff
MESSAGE
ANALOG IN DIFF 1-
2
Range: 1<>2, 1>2, 2>1
MESSAGE
ANALOG IN DIFF 1-
2
Range: Always, Start/Run
MESSAGE
A/I DIFF 1-2
BLOCK
Range: 0 to 5000 s in steps of 1
MESSAGE
ANALOG IN DIFF 1-
2
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS:
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
MESSAGE
ANALOG IN DIFF 1-
2
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
MESSAGE
ANALOG IN DIFF 1-
2
Range: 0.1 to 300.0 s in steps of 0.1
MESSAGE
ANALOG IN DIFF 1-
2
Range: On, Off
MESSAGE
ANALOG IN DIFF 1-
2
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP
RELAYS:
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3 Trip & Auxiliary3
MESSAGE
ANALOG IN DIFF 1-
2
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
MESSAGE
ANALOG IN DIFF 1-
2
Range: 0.1 to 300.0 s in steps of 0.1
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...