5–92
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Table 5–3: Analog Output Parameter Selection Table
PARAMETER NAME
RANGE / UNITS
STEP
DEFAULT
MIN.
MAX
Phase A Current
0 to 100000 A
1
0
100
Phase B Current
0 to 100000 A
1
0
100
Phase C Current
0 to 100000 A
1
0
100
Avg. Phase Current
0 to 100000 A
1
0
100
AB Line Voltage
50 to 20000 V
1
3200
4500
BC Line Voltage
50 to 20000 V
1
3200
4500
CA Line Voltage
50 to 20000 V
1
3200
4500
Avg. Line Voltage
50 to 20000 V
1
3200
4500
Phase AN Voltage
50 to 20000 V
1
1900
2500
Phase BN Voltage
50 to 20000 V
1
1900
2500
Phase CN Voltage
50 to 20000 V
1
1900
2500
Avg. Phase Voltage
50 to 20000 V
1
1900
2500
Hottest Stator RTD
–50 to +250
°
C or –58 to +482
°
F
1
0
200
Hottest Bearing RTD
–50 to +250
°
C or –58 to +482
°
F
1
0
200
Ambient RTD
–50 to +250
°
C or –58 to +482
°
F
1
-50
60
RTD #1 to 12
–50 to +250
°
C or –58 to +482
°
F
1
-50
250
Power Factor
0.01 to 1.00 lead/lag
0.01
0.8 lag
0.8 lead
Reactive Power
-50000 to 50000 kvar
1
0
750
Real Power
-50000 to 50000 kW
1
0
1000
Apparent Power
0 to 50000 kVA
1
0
1250
Thermal Capacity Used
0 to 100%
1
0
100
Relay Lockout Time
0 to 500 min.
1
0
150
Current Demand
0 to 100000 A
1
0
700
kvar Demand
0 to 50000 kvar
1
0
1000
kW Demand
0 to 50000 kW
1
0
1250
kVA Demand
0 to 50000 kVA
1
0
1500
Motor Load
0.00 to 20.00 x FLA
0.01
0.00
1.25
Analog Inputs 1-4
–50000 to +50000
1
0
+50000
Tachometer
100 to 7200 RPM
1
3500
3700
Summary of Contents for 469
Page 62: ...2 16 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 2 INTRODUCTION ...
Page 90: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Page 292: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Page 313: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 7 HGF5C 808841A1 HGF8 808842A1 ...
Page 315: ...A APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A 9 808712A1 CDR ...
Page 320: ...A 14 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL A APPENDIX ...