CHAPTER 4: PROGRAMMING
239 MOTOR PROTECTION RELAY – INSTRUCTION MANUAL
4–57
turned off via the
SIMULATION ON/OFF
setpoint or via the serial port or until control
power is removed from the 239.
4.8.7
RTD Simulation
•
SIMULATION:
Enter ON to switch from actual input to the programmed simulation
temperature value of each RTD input value. While simulation is on all three RTD r
inputs will be overridden by the simulated temperature values. Set this setpoint to
OFF
after simulation is complete. As a safeguard, simulation will automatically turn
off if:
•power to the 239 is turned off and on
•time programmed in
S5: TESTING\RTD SIMULATION\SIMULATION
ENABLED FOR
setpoint has elapsed since simulation was first enabled
When RTD simulation is turned on the following flash message will be displayed for 3
seconds.
When RTD simulation is turned off the following flash message will be displayed for 3
seconds.
•
RTD 1/2/3 TEMPERATURE:
Enter the value of the each RTD temperature to be
simulated. The functionality of the RTDs remains as is with actual inputs connected to
the 239.
•
SIMULATION ENABLED FOR:
Select the desired length of time that simulation will be
enabled. When the programmed time has elapsed, RTD simulation will turn off. If
UNLIMITED
is selected, simulated RTD input will be used until simulation is turned off
via the
SIMULATION ON/OFF
setpoint or via the serial port or until control power is
removed from the 239.
4.8.8
GE Multilin Use Only
•
SERVICE PASSCODE CODE:
These messages are accessed by GE Multilin personnel
only for testing and service.
SIMULATION
HAS BEEN ENABLED
RTD SIMULATION
HAS BEEN DISABLED
Summary of Contents for Multilin 239
Page 6: ...TOC 4 369 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 20: ...1 14 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 1 OVERVIEW ...
Page 48: ...3 10 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Page 96: ...4 58 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 4 PROGRAMMING ...
Page 108: ...5 70 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 5 MONITORING ...
Page 150: ...7 112 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING ...
Page 152: ...A 2 239 MOTOR PROTECTION RELAY INSTRUCTION MANUAL CHAPTER A ...