32
!
Figure 3.9
3.1.8
OPTIONAL 24VDC 150 WATT POWER SUPPLY
The C1 Controller may be powered from 10-30VDC. However, many applications
require 24VDC power for the monitors or transmitters providing inputs to the C1. A 150
watt AC / DC power supply may be included for these applications (115VAC or 230
VAC selected via slide switch). When ordered from the factory, it is pre-wired to
provide 24VDC primary power for the C1 controller as well as any transmitters or
monitors that may be connected by the end user.
Figure 3.8
SECTION 4
4.0 SYSTEM DIAGNOSTICS
A
System Diagnostic Mode
shown in Figures 4.1 and 4.2 may be entered during normal
operation from the Setup menu. The entry menu indicates firmware revision and offers
useful routines for testing front panel LED’s, relays, serial ports and analog I/O. It is
exited manually by pressing
NEXT
and automatically if no keys are pressed for 5
minutes. It is very important to understand that
CHANNEL INPUT DATA
IS NOT PROCESSED DURING THE DIAGNOSTICS MODE
. It is
possible to miss important input values while utilizing this mode and
appropriate safeguards should be in place. However, the Diagnostics Mode
Summary of Contents for C1