TB2
+
-
5VDC ONLY!
ASSY# 10-0195 8-CH DISCRETE RELAY
TB1
JUMPERS
ZONE
JP4
U2
J2
J3
Ch6
Ch7
Ch5
Ch8
Ch3
Ch1
Ch2
Ch4
S1 controls if discrete relays are tripped by
A1, A2, or A3 alarms for Ch’s 1-8 or 9-16.
See Chart.
JP4 allows “zoning” of adjacent
channel alarms. All zoning jumpers
are placed vertically. Dwg. exhibits
channels 1-4 and channels 5-7
creating 2 zones. All relays in a zone
switch together. Unused jumpers
may be stored horizontally.
J2 & J3 are interchangable I2C
connectors used to add option
PCB assemblies to the controller.
TB2 is used to supply external
5VDC power to Alarm boards
when they are mounted > 5
feet from the controller. I2C
cables provide 5VDC but losses
occur with longer cable lengths.
WARNING: Voltages exceeding
6 volts may cause extensive
damage to entire controller.
CH1/9
CH3/11
CH7/15
CH5/13
NC
NO C
NO
NC
C
NO
NO C
NC
C
NC
CH2/10
CH4/12
CH8/16
CH6/14
NC
NO C
NO
NC
C
NO
NO C
NC
C
NC
5 amp form C dry contacts. Contacts are unfused. Switching
inductive loads may create high levels of RFI. Use appropriate
“RFI Snubbers” on inductive load devices.
8 Channel Discrete Relay Option #10-0195
U1
U3
Q2
SB1
SB2
0
WITH 8 RELAYS:
S1 selects Ch’s 1-8
or 9-16 for A1, A2 &
A3 (Flt) See chart--->
S1
S1-2=Ch9-16 A1
S1-3=Ch9-16 A2
S1-4=Ch9-16 A3
S1-5=Ch1-8 A1
S1-6=Ch1-8 A2
S1-7=Ch1-8 A3
8-CH CHART
Wire TO CPU
5VDC if > 5’
from controller
Install
vertically
to create
Ch. zones
Standard configuration has a 1
minute POWER ON time delay
preventing relay actuation during
the delay. SB1 increases delay
time to 8-minutes. SB2 removes
all time delay.
Figure 3.4
3.1.3 OPTIONAL
*BRIDGE
SENSOR INPUT BOARD #10-0191
An optional 8-channel, 12 bit
Bridge Sensor Input
board allows these popular gas
detectors to be connected directly to the C1 without additional signal conditioning or
transmitters. Up to four dual channel 10-0192 modules may be installed in each 8-
channel 10-0191. Each 10-0192 channel is equipped with a bridge amplifier and balance
potentiometer and an adjustable switching regulator for setting the correct sensor
excitation voltage. A 3 position coarse gain jumper allows setting the gain of the bridge
amplifier. Fault supervision circuitry forces the C1 into a FAULT condition upon sensor
failure or removal.
This option may also be configured to accept 4-20mA inputs for mixing bridge sensors
and current loops into the same board. Placing any channel’s 2 position LEL/4-20mA
jumper into 4-20mA position and installing the associated precision 100 ohm socketed
resistor allows 4-20mA signals to be applied to it’s C & A terminals. The 10-0192 sensor
modules are not required for channels accepting 4-20mA.