TECHNICAL DATA
Type
GDH240-Air
Certificate and protection
CE / IP24
Installation location
Indoor / Outdoor
Operation temperature limits
Air
ºC
-25 to +35
Heat water flow
ºC
Up to 60
Heating capacity / COP
Outlet water temp. A10/35
31.80 kW / COP 4.1
Outlet water temp. A7/35
29.60 kW / COP 3.8
Outlet water temp. A2/35
24.20 kW / COP 3.4
Outlet water temp. A-7/35
19.4 kW / COP 2.7
Cooling capacity / COP
Outlet water temp. A30/18
21.3 kW / COP 2.8
Sound pressure level at distance
dB(A)
42
Heat carrier flow nominal
m
3
/h
4.8
Internal pressure drop heat carrier
kPa
30
Air flow
m
3
/h
11600
Compressor type
2x Scroll
Refrigerant R404A
kg
5.2
Control Voltage
V
230
Supply Voltage
400V 3-N, 50 HZ
Nominal power consumption at A2/W35
KW
7.8
Starting current
A
2x 60 or 2x 25 with soft starter
Nominal current
A
25
Nominal current at A2/W35
A
15.4
Device connection to heating system
Inch
G1 1” external
Type of defrosting
Reverse cycle
Dimensions
Size (H X W X D)
mm
1.500 x 1.380 x 650
Weight
kg
360
Summary of Contents for GDH70-Air
Page 5: ...DIMENSIONS GDH70 Air GDH120 Air GDH240 AIR...
Page 8: ......
Page 9: ...ELECTRIC INSTALLATION GDH70 AIR GDH120 Air GDH240 Air...
Page 10: ...GDH200 CONTROLLER INSTALLATION...
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ...APPENDIX ELECTRICAL WIRING DIAGRAM GDH70 AIR...
Page 15: ...GDH120 AIR...
Page 16: ...GDH240 AIR...
Page 17: ...DIMENSIONS GDH70 AIR GDH120 AIR...
Page 20: ......
Page 21: ......
Page 22: ......