background image

3

 

GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

 

Full DC Inverter CHV System - Control System

 

16 

Port for inlet temperature sensor of plate heat exchanger 

32 

 

1.2 Dial codes definition 

 

 

 

SW4 

Parameter setting for night time silent operation 

Meaning 

After 

6

 hours of daytime 

peak temperature, night 
time silent operation start, 
last for 

10

 hours, then 

return to normal operation. 

After 

8

 hours of daytime 

peak temperature, night 
time silent operation start, 
last for 

10

 hours, then 

return to normal operation. 

After 

6

 hours of daytime 

peak temperature, night 
time silent operation start, 
last for 

12 

hours, then 

return to normal operation. 

After 

8

 hours of daytime 

peak temperature, night 
time silent operation start, 
last for 

8

 hours, then return 

to normal operation. 

Demonstration 

 

(Default setting) 

 

 

 

 

Remarks 

 

It is available only when user turn on the night time silent operation mode in SW8. 

 

Night time silent operation mode is default ON. 

 
 
 
 
 
 
 
 

Summary of Contents for GCHV-E252W/ZR1

Page 1: ...Full DC Inverter CHV System Control System Technical Support Division 2020 11 21 GD CHIGO HEATING VENTILATION EQUIPMENT CO LTD...

Page 2: ...1 GD CHIGO HEATING VENTILATION EQUIPMENT CO LTD Full DC Inverter CHV System Control System 1 Outdoor Unit PCB 2 Communication System 3 Controllers Content...

Page 3: ...witch 22 Port for electric heater of compressor A 7 Input port for signal of high pressure switch 23 Output port for solenoid valves 8 Control port of DC fan left fan and single fan use port 1 24 Outp...

Page 4: ...l operation After 8 hours of daytime peak temperature night time silent operation start last for 10 hours then return to normal operation After 6 hours of daytime peak temperature night time silent op...

Page 5: ...n motor will turn on for 30 seconds Meaning 1 System can be start only after power on for 12 minutes 2 Snow blowing function is OFF 1 System can be start only after power on for 7 minutes 2 Snow blowi...

Page 6: ...HP 16HP 18HP 20HP 22HP Point to 0 Point to 1 Point to 2 Point to 3 Point to 4 Point to 5 Point to 6 Point to 7 SW2 Forced cooling button 1 After pressing it once all indoor units and outdoor units wil...

Page 7: ...demand of indoor units Only available for master unit 13 Outdoor unit actual capacity output Actual output HP 14 Low pressure value Actual value Display value 0 1 MPa 15 High pressure value Actual va...

Page 8: ...T2B target value A for cooling mode 5 15 8 is factory default value 45 T2 target value B for heating mode 40 50 44 is factory default value 46 Power saving value 0 100 1 90 2 80 3 70 4 60 5 50 6 40 4...

Page 9: ...r the error code H5 There is 3 times P2 protection in 60 minutes Repower on to clear the error code H6 There is 3 times P4 protection in 100 minutes Repower on to clear the error code H7 Indoor unit q...

Page 10: ...setting will be saved automatically After 20s without any operations it will automatically return to the frequency display or standby display SH1 Cooling T2B target value A unit range 5 15 the factor...

Page 11: ...tage side of unit should be less than 2 If its length could not be shortened thicken the power wire Voltage discrepancy between phases shall not pass 2 rated value and Current discrepancy between high...

Page 12: ...ity Model Power supply The shortest wiring diameter mm2 Manual switch A Circuit breaker 20m 50m GND Capacity Fuse GCHV E252W ZR1 380 415V 3 Phase 50Hz 4 6 4 10 6 32 32 100mA 0 1sec GCHV E280W ZR1 4 6...

Page 13: ...e following requirement a Diameter of main wire a depends on the total horse power HP of outdoor unit See 5 Example In system 8HP 1 unit 8HP 1 unit 10HP 1 unit So totally 26HP See 5 size of wire is 25...

Page 14: ...100 100 74 76 250 250 30 34 100 100 78 88 400 310 5 Reference table of the cable size for each capacity Total capacity HP Minimum wire diameter mm2 Total capacity HP Minimum wire diameter mm2 Wire le...

Page 15: ...etween indoor indoor unit and that between outdoor outdoor units into one system Please do not put the signal wire and power wire in the same wire tube keep distance between the two tubes Current capa...

Page 16: ...not be bound together with refrigerant pipeline and power wire When power wire and control wire is distributed in parallel form keep gap between them above 300mm so as to preventing signal interferenc...

Page 17: ...EQUIPMENT CO LTD Full DC Inverter CHV System Control System Signal line shall adopt 2 core shielded wire with an area above 0 75 mm2 the 2 cores are connected to P Q or H1 H2 terminals the shielded la...

Page 18: ...r cable Outdoor unit power cable Power distributor Power distributor Power distributor Note The signal connecting line between outdoor units indoor and outdoor units and indoor units has polarity When...

Page 19: ...System 2 1 4 Correct connection Note Shielded layer should be connected to steel pane of electrical control box 2 1 5 Typical wrong connection 1 Loop connection of signal wire 2 Star connection of sig...

Page 20: ...19 GD CHIGO HEATING VENTILATION EQUIPMENT CO LTD Full DC Inverter CHV System Control System 3 Reverse connection of signal wire a Outdoor unit to indoor unit b Indoor unit to indoor unit...

Page 21: ...erature Temperature addition Increase the setting temperature Mode Select modes including automatic cooling dehumidification fan and heating mode Fan speed Increase fan speed in one gear Highest wind...

Page 22: ...uction of LCD screen icon Mode display automatic cooling dehumidification fan and heating Temperature display displays temperature which range between 16 32 C or 61 90 Wind speed display means wind sp...

Page 23: ...ting when pressing this key the setting temperature will be added by 1 The temperature of centigrade model will be added progressively by 16 17 31 32 The temperature of Fahrenheit model will be added...

Page 24: ...opening ECON mode Switching mode will close ECON mode 12 Sleep Pressing this key in the modes except of the fan mode the sleep function switches between opening and closing Switching mode will cancel...

Page 25: ...rameters setting 2 The methods and instructions of displaying indoor unit s address Ducted type indoor unit with a wired controller Execute address query operation or press the CHECK key of wired cont...

Page 26: ...Confirm there is no abnormal phenomenon during test operation after installation completed then hand the manual to the user 3 Installation must be conducted by professionals 4 Improper installation m...

Page 27: ...nnecting between wire controller and indoor unit Circuit of wire controller is low voltage circuit Never connect it with a standard 220V 380V circuit or put it into a same wiring tube with the circuit...