6. Detector Operation Flow
6. Detector Operation Flow
GTD-3000TxW
Instruction Manual
6.3. Operation Flow
■ After power on, it passes self-diagnostic process then enters Measuring Mode. Here, by operating front keys, you can
go to internal System Mode.
■ Timeout for Level1 and Level2 are 10 s. It is set to 1 h for Level2 Calibration and Test Mode.
■ When "RESET" key contacts at Program Mode Screen, it returns to Measuring Mode. When "RESET" key contacts at
each Program Setting Screen, it returns to the parent step.
[Figure 13. GTD-3000TxW Mode Configuration]
[Table 8. Operation Key Description]
ITEM
NAME
DESCRIPTION
FUNC
Function key
Detector Mode Setting Entry Function (Insert Magnetic-bar for 2 sec or longer in measuring mode)
Level2 next stage entry function and setting value saving function
RESET
Reset key
Move to the previous stage from the level entered.
↑
Up key
Next level mode that is configured in LEVEL1 and Change in Level2 setting Plus
↓
Down key
Next level mode that is configured in LEVEL1 and Change in Level2 setting Minus
■ Operation keys for detector system mode are defined as below.
6.4. Menu Configuration Table
LEVEL1
LEVEL2
DEFAULT
NAME
PARAMETER
PROGRAMMABLE
MODE
GAS TYPE
[DEFINE/USERG.]
DEFINE
GAS SELECT
Factory Set
COMB.
UNIT SELECT
%/%LEL/PPM/PPB
%LEL
DECIMAL POINT
0.100/1.00/10.0/100
100
HIGH SCALE
1~9999
100
PASSWORD
00~99
00
CALIBRATION
MODE
CALIBRATION
[ZERO]
ZERO CALIBRATION
[NO, YES]
[NO]
ZERO GAS
[ 0]
ZERO PROCESSING
[SUCCESS / FAIL]
CALIBRATION DATA
[ 0 / FAIL]
CALIBRATION
[SPAN]
SPAN CALIBRATION
[NO, YES]
[NO]
SPAN GAS VALUE
[ 0]
SPAN SET VALUE
[50 / FAIL]
50
SPAN PROCESSING
[SUCCESS / FAIL ]
CALIBRATION DATA
[ 0]
ALARM PROGRAM
MODE
ALARM OPERATING
[AUTO/MANUAL]
AUTO
ALARM RELAY TYPE
DE-ENERGIZED/ENERGIZED
DE-ENERGIZED
FAULT RELAY TYPE
DE-ENERGIZED/ENERGIZED
DE-ENERGIZED
ALARM1 TYPE SEL.
(ALARM1 TYPE SELECT)
[INCREASE/ DECREASE]
INCREASE
ALARM1 LEVEL ADJ
(ALARM1 LEVEL ADJUST)
[ 1~Full Scale]
20
ALARM1 DEAD BAND
[ 0.0~ Full Scale의 10% ]
0.0
ALARM1 TIME SET
[0~60] SEC
1
ALARM1 RELAY CTL
(ALARM1 RELAY CONTROL)
[ON / OFF]
ON