7. System Mode
7.3. ALARM MODE
PASSWORD
[**]
- Contacting "FUNC" key with the Magnet-bar for 2 s or longer in Measuring Mode enters Password
mode.
- After setting Password using "↑" or "↓" key, contact "FUNC" key.
ALARM PROGRAM
MODE
- Contact "↑" or "↓" key to select "Alarm Program Mode".
- Contact "FUNC" key when "ALARM PROGRAM MODE" is displayed to enter Alarm setting mode.
- Contact "RESET" key to return to Measuring Mode.
ALARM OPERATING
[ AUTO ]
- It is a mode that sets reset method after an event of alarm. Contacting "↑" or "↓" key changes between
"AUTO" and "MANUAL".
- "AUTO" mode automatically resets the alarm. "MANUAL" mode resets the alarm only when Reset key is
pressed.
ALARM OPERATING
[ MANUAL]
ALARM RELAY TYPE
DE-ENERGIZED
- It is a mode that sets Reset method after an event of Alarm. Contacting "↑" or "↓" key changes between
"DE-ENERGIZED" and "ENERGIZED".
- "DE-ENERGIZED" deactivates energizer mode and "ENERGIZED" activates energizer mode.
FAULT RELAY TYPE
DE-ENERGIZED
- It is a mode that sets Reset method after an event of FAULT. Contacting "↑" or "↓" key changes
between "DE-ENERGIZED" and "ENERGIZED".
- "DE-ENERGIZED" deactivates energizer mode and "ENERGIZED" activates energizer mode.
ALARM1 TYPE SEL.
[INCREASE ]
- It is a mode that sets operational direction of Alarm1. Contact "↑" or "↓" key to display "INCREASE" or
"DECREASE".
- "INCREASE" mode runs when the value is at Alarm1 threshold or higher. "DECREASE" mode runs when
the value is at Alarm 1 threshold or lower.
ALARM1 TYPE SEL.
[DECREASE ]
ALARM1 LEVEL ADJ
[ 20]
- It is a mode that sets Alarm1 level threshold. Contact "↑" or "↓" key to increase or decrease Alarm1
level, respectively.
- When a desired alarm 1 threshold is displayed, contact “FUNC” key to set it and enter the next item.
ALARM1 DEAD BAND
[ 0.0]%FS
- It is a mode that sets operation range of Alarm1. Contact "↑" or "↓" key to increase or decrease the
value, respectively.
- When Alarm1 is in "INCREASE" mode, it runs at Alarm1 thr Dead band and is released at
Alarm1 threshold - Dead band.
- When a desired value is displayed, contact "FUNC" key to set the dead band value and enter the next
Alarm Program Mode
ALARM1 TIME SET
[ 1] SEC
- It is a mode that sets Alarm1 dwell time. Contact "↑" or "↓" key to increase or decrease the value,
respectively.
- Displayed number is in sec and in a range from 0 to 60. When a desired value is displayed, contact
"FUNC" key to set the alarm dwell time and enter the next Alarm Program mode.