GTC-550

Instruction Manual

■ Check wirings for operation power, detection parts, alarm parts, and concentration display.

■ Check the power input then turn ON the power S/W.

■ Check whether power LED at alarm and concentration display parts light on.

■ Check whether "SELF" is displayed on FND concentration display part.

6.1. Power ON

- After GTC-550 power turns ON, the current firm ware version is displayed.
- VER is displayed for 0.5 sec on FND then number displays.
- The current version is 2.09.

- After warming-up by "SELF" flashing for approx. 30 sec on FND of concentration display, 

it immediately enters the measurement mode.

- Upon an event of fault of the equipment or detector at this time, fault alarm appears.

- Displays gas concentration received by the detector on FND digital display in numbers.

- When the detector is not connected or input current from the detector is under 10% below the 

set high scale value, "Undr" displays and flashes at 1 sec interval

- Trouble LED lights on, warning light flashes, and buzzer sounds

- When "BZSTOP" S/W is pressed, warning light lights on and buzzer stops

- When the input current from the detector is over 10% above the set high scale value, "ovE" 

displays and flashes at 1 sec interval.

- Alarm 1, 2, 3 LED lights flickers, warning light flickers, and buzzer sounds.

- When "BZSTOP" S/W is pressed, warning light lights on and buzzer stops

- When gas concentration is detected to be above the set value for alarm, alarm function counts  

the dwell time and if it is above the set dwell time, alarm function operates.

- Alarm relay turns on when it is above the alarm dwell time.

- When Alarm Latch Type is at "ON" mode and alarm function runs, the alarm status and gas  

concentration value stays at the maximum value. When gas concentration decreases below 

the alarm value, alarm does not get released and "RESET" S/W must be ran to release it.

- When Alarm Latch Type is OFF, Alarm is released automatically in accordance to gas 

concentration.

X.XX

■ Pressing "TEST" S/W for 2 sec or longer in gas concentration display mode enters Test mode.

■ In test mode, when it passes 30 min after the last S/W control, it automatically returns to the gas concentration  

  display mode.

6.2. Test Mode

- When it enters Test mode, gas concentration number displays and flickers.
- This function enables testing without injecting gas to the detector sensor. The user can set 

an arbitrary concentration by pressing "Test" S/W and alarm function operates normally with 

a user-defined concentration.

- When "FUNC" S/W is pressed 2 sec or longer, it enters FND / LED Test function.
- When "RESET" S/W is pressed, it returns to gas concentration display mode.

▼ ▲

Full Range

■ Pressing "DOWN" S/W for 2 sec or longer in gas concentration display mode enters Stand-by mode.

■ When ETO (Emergency Time Out) is set to ON in Option Setting Mode, it automatically returns to gas 

  concentration display mode after 30 min.

■ When ETO is OFF, "DOWN(Stand-by)" S/W must be pressed 2 sec or longer to return to gas concentration 

  display mode.

6.3. Stand-by Mode

- In stand-by mode, STD-BY LED flickers. Trouble/Alarm relay of GTC-550 contact output 

does not operate but all other functions run.

- When "DOWN(Stand-by)" S/W is pressed 2 sec or longer, it returns to gas concentration 

display mode

6. Operation Method

6. Operation Method

Summary of Contents for GTC-550

Page 1: ...AdvancedIndustry1 ro Bugok dong Gunpo si Gyeonggi do Tel 82 31 490 0800Fax 82 31 490 0801 Yeongnambusinessoffice Plant 55Gonghangap gil85beon gil Gangseogu BusanMetropolitanCity Tel 51 973 8518Fax 51 973 8519 E mail info gastron com www gastron com Read in detail for correct use ...

Page 2: ...ed quarterly when the calibration period is not specified In case of a problem after purchasing the product please contact the address below Address 23 Gunpo Advanced Industry 1 ro Gunpo si Gyeonggi do Tel 031 490 0800 Fax 031 490 0801 URL www gastron com e mail info gastron com The product and manual are subject to change without a notice for the product s functional improvement and ease of use F...

Page 3: ...pecifications Standard Type 8 3 4 Environmental Specifications 8 4 Name and Description of Each part 9 5 Installation 12 5 1 Power Configuration 12 5 2 Signal Terminal Configuration 13 5 3 Relay Terminal Configuration 14 5 4 3 wire Type Gas detector Connection Method 15 5 5 2 wire Type Gas detector Connection Method 15 6 Operation Method 16 6 1 Power ON 16 6 2 Test Mode 17 6 3 Stand by Mode 17 6 4...

Page 4: ...e it has an output for an error SPDT contact GTC 550 receiver provides 4 20mA DC output for the measured value and is able to communicate digitally using RS 485 network signal Option ITEMS SPECIFICATION Measuring Value Display 3 inch 3 3 Digit FND Measuring Range Capable to display 00 0 999 Alarm Indicator Visible Indicator 3 Alarm Trouble LED Warning Light Audible Indicator Buzzer Signal 85 dB Al...

Page 5: ...s 0 2mA Measured value signal 4mA Zero to 20mA Full Scale Fault 0 100 LEL 100 109 LEL Over 110 LEL Maintenance 0mA 4mA 20mA 21 6mA 20mA 21 4mA 3mA Analog output current ripple noise max 20uA Relay Contact Alarm1 Alarm2 Alarm3 Fault Relay AC250V 5A Relay contact SPDT Wiring requirement Power CVVS or CVVSB with shield Analog CVVS or CVVSB with shield RS485 STP Shielded Twisted Pair Cable Connection ...

Page 6: ...e the set value or to select the previous setting When a value needs to be changes in a large range pressing DOWN S W for a certain time changes the value rapidly 16 TEST S W Pressing TEST S W enters a mode that performs self test Measurement FND flickers and the value can be adjusted using UP S W and DOWN S W to check the alarm operation status To release self test press RESET S W 17 RESET S W Pe...

Page 7: ...vely After detaching the equipment cover terminal block that connects power and various signals within PCB appears Connect AC Power 85 260 V 50 60 Hz to CN9 as shown in the figure below 5 2 Signal Terminal Configuration Using CN6 terminal connect 4 20 mA output External Reset RS485 and external gas detector Terminal configuration is as shown in the table below RS 485 cable uses a cable designated ...

Page 8: ...hield cable with CVVSB 0 7 sq or higher Our gas detector models in this type are TS 1100Ex TS 2000Ex TS 2100 Series TS 4000 Series TS 4100P Series TS 5100 Series GTD 1000 Series GTD 2000 Series GTD 3000 Series GIR 3000 Series When the gas detector output has 2 wire V V connect to the Channel Unit as shown in Figure 6 Connecting cable must comprise of CVVS or shield cable with CVVSB 0 7 sq or highe...

Page 9: ...n operates Alarm relay turns on when it is above the alarm dwell time When Alarm Latch Type is at ON mode and alarm function runs the alarm status and gas concentration value stays at the maximum value When gas concentration decreases below the alarm value alarm does not get released and RESET S W must be ran to release it When Alarm Latch Type is OFF Alarm is released automatically in accordance ...

Page 10: ... Relay ON OFF ON Alarm 2 Blink ON OFF OFF Alarm 3 1 Full range 50 F R 3H H L H 3H 00 0 99 00 Alarm 3 Time Delay 0 60 0 Alarm 3 Relay ON OFF ON Alarm 3 Blink ON OFF OFF End Table 4 Mode Setting Table PROGRAM MODE ALARM MODE LEVEL1 LEVEL2 LEVEL3 LEVEL4 Range available for Selection DEFAULT FUNC FUNC FUNC FUNC END U P D O W N P A S S W O R D I N P U T U P D O W N Maintenance Level U P D O W N 0 Full ...

Page 11: ...ram setting function when it passes 10 s after the last S W control it automatically returns to gas concentration display mode When FUNC S W is pressed it enters Program Mode When RESET S W is pressed it returns to gas concentration display mode It is gas selection function that can be selected by gas type When FUNC S W is pressed it enters Gas Selection Mode When RESET S W is pressed it returns t...

Page 12: ...ode changes when UP or DOWN S W are pressed When ON the actual gas mA value is displayed in any mode entered When OFF mA corresponding to each mode is outputted as the same as existing setting When a desired out set mode is displayed press FUNC S W to set it and enter the next item When RETURN S W is pressed it returns to Program Mode 6 4 3 ALARM Mode After setting a password move to UP S W or DOW...

Page 13: ...next item When RESET S W is pressed it returns to Alarm Setting Mode Default Alarm1 20 F S 20 Alarm2 40 F S 40 Alarm3 50 F S 50 Alarm level is set to the concentration outlined in domestic regulations as factory setting It is a mode to set a direction of Alarm 1 operation Pressing UP S W or DOWN S W displays H or L respectively H mode operates when gas value is equal or greater than Alarm1 setting...

Page 14: ...mode Alarm 1 blink output does not run In ON mode it runs However it runs when Alarm1 contact output mode is ON When a desired Alarm 1 blink output mode is displayed press FUNC S W to set it and enter the next item When RESET S W is pressed it returns to Alarm Setting Mode A message indicating completion of setting is displayed as End for 2 sec then it returns to gas concentration display status A...

Page 15: ...ing is displayed as End for 2 sec then it returns to gas concentration display status 6 4 5 Test Mode After setting a password move to UP S W or DOWN S W then press FUNC S W to enter the mode In test mode when it passes 10 sec after the last S W control it automatically returns to gas concentration display mode Test mode enables testing without injecting gas to the detector sensor The user can set...

Page 16: ...essed it enters Option setting mode When RESET S W is pressed it returns to gas concentration display mode It is channel Number Setting Function that sets Serial Number of Control Unit Press FUNC S W to enter Channel number setting function When RESET S W is pressed it returns to gas concentration display mode Full Range Channel number is a mode that enters serial number of control unit to enable ...

Page 17: ...ESET and TEST S W for 2 sec or longer in gas concentration display mode enters Maintenance mode RESET S W must be pressed in Maintenance mode to return to gas concentration display mode Mode that selects function to set current input and output values that are reference of Channel unit Pressing UP S W or DOWN S W displays In or oUt respectively When a desired mode is displayed press FUNC S W to se...

Page 18: ...ration display mode It is a mode that tests output current after calibration Default 4 0 It can confirm a range for 3 0 mA 21 0 mA with UP S W and DOWN S W Pressing FUNC S W after confirmation goes to the next item When RESET S W is pressed it returns to gas concentration display mode A message indicating completion of setting is displayed as End for 2 sec then it returns to gas concentration disp...

Page 19: ...t Integer Decimal point is not considered High Scale Setting 30002 BIT15 0 High Scale Setting Integer Decimal point is not considered Alarm 1 Setting 30003 BIT15 0 Alarm 1 Setting Integer Decimal point is not considered Alarm 2 Setting 30004 BIT15 0 Alarm 2 Setting Integer Decimal point is not considered Gas detector status value 10000 BIT0 Alarm 1 Active Status BIT1 Alarm 2 Active Status BIT2 Fau...