![GASTRON GTC-520A Instruction Manual Download Page 8](http://html.mh-extra.com/html/gastron/gtc-520a/gtc-520a_instruction-manual_569025008.webp)
5.3. Configuration of Relay terminal
www.gastron.com
14
_
15
5. Installation
5. Installation
GTC-520A
Instruction Manual
FUNCTION
PIN
TERMINAL NAME
DESCRIPTION
Alarm1
1
NO
Alarm1 Normal Open
2
NC
Alarm1 Normal Closed
3
COM
Alarm1 Common
Alarm2
4
NO
Alarm2 Normal Open
5
NC
Alarm2 Normal Closed
6
COM
Alarm2 Common
Alarm3
7
NO
Alarm3 Normal Open
8
NC
Alarm3 Normal Closed
9
COM
Alarm3 Common
Trouble
10
NO
Trouble Normal Open
11
NC
Trouble Normal Closed
12
COM
Trouble Common
LP
13
+
Outside power supply (DC24V) + output
14
-
Outside power supply (DC24V) - output
[Table 3.Description of CN5 terminal]
[Figure 4. Configuration of CN5 terminal]
5.4. How to connect 3-wire type Gas detector
5.5. How to connect 2-wire type Gas detector
[Figure 5. 3-wire type gas detector]
[Figure 6. 2-wire type gas detector]
■ When the gas detector is configured with 4-20mA output, connect
with the Channel Unit by the method shown on the right side.
■ Connecting cable should be configured with shield cable of
CVVS or more than CVVSB 0.7sq.
■ Our company's detector models of the relevant method include
TS-1100Ex, TS-2000Ex, TS-2100 Series, TS-4000 Series,
TS-4100P Series, TS-5100 Series, GTD-1000 Series, GTD-
2000 Series, GTD-3000 Series, and GIR-3000 Series.
■ When output of gas detector is configured with 2-wire(V+,V- ),
connect with the Channel Unit by the following method.
■ Connecting cable should be configured with shield cable of
CVVS or more than CVVSB 0.7sq.
■ Our company's detector models of the relevant method include
TS-1100Tx, TS-2000Tx, TS- 3000 Series, and TS-3100 Series.
■ By using CN5 terminal, it is configured with 3 ea of SPDT-type Alarm relay, and 1ea of SPDT -type Trouble relay.
■ Alarm Lamp(LP) can be connected with DC outside warning light.
■ To use outside DC warning light or outside device, LP terminal outputs DC +24V power supply irrespective of
AC, DC power supply mode.