11.3.
How to use INSPECTION MODE
This Mode is used for the inspector to identify the detector status and Fault details without
affecting the equipment operated in emergency. Only authorized personnel are allowed to use
this Mode.
Press and hold the
"↓" Switch
for at least 3 seconds while
Means value display gas concentrations in the display. Press and
hold the
"↓" Switch
for at least 3 seconds to exit again.
Entering Inspection Mode, '<' mark will flash at the first place in
the second row.
You can enter M.-LEVEL item from Maintenance Mode to set
Output value.
11.4.
Data initialization
Only authorized personnel are allowed to conduct this Mode because it will initialize all the
values to the data set in the factory before shipping.
Turn the power ON while holding "FUNC" Key and "UP" Key.
When " TSM,SEN INIT " is displayed on the Display window, select
"YES" to carry out the data initialization.
11.5.
Correction data initialization
Only authorized personnel is allowed to conduct the initialization because this Mode initializes
to the value of Calibration data set in the factory before shipping. This Mode is used for the
inspector to initialize only the Calibration value among setting values.
Turn the power ON while holding "FUNC" Key and "UP" Key.
When " SEN CAL INIT " is displayed on the Display window, select
"YES" to carry out the normal initialization of Calibration data.
SEN CAL INIT
[ YES ]
TSM,SEN INIT
[ YES ]