For more information & Technical support:
22
F-Guard UV-IR User Manual
Doc. No. F110V0020.06
T
ABLE
2:
D
ETECTOR
C
ONFIGURATION
O
PTIONS
Function
Options
Default Setting
Sensitivity
Low, Medium, High, Extreme
Medium
Ultra-fast detection
Disabled, Enabled
Disabled
Alarm Delay
0, 5, 10, 20 or 30 seconds
0 seconds (no delay)
Alarm Latch
Disabled, Enabled
Disabled
Enable Pre-Alarm 0-20mA
Disabled, Enabled
Disabled
Enable dirty window warning 0-
20mA
Disabled, Enabled
Disabled
Aux. Relay
Alarm
Pre-Alarm
UV Detected
IR Detected
Dirty Window Warning
Alarm
Window Heater
Disabled, Enabled
Enabled
Modbus address
1 – 247
1
Manual BIT – Alarm Output Test
Disabled, Enabled
Disabled
•
Note:
Medium sensitivity setting allows detection of a 1x1ft
2
(0.1m
2
) N-heptane pan fire
at a distance of 50ft (15m).