For more information & Technical support:
11
F-Guard UV-IR User Manual
Doc. No. F110V0020.06
•
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel per the applicable code of practice.
•
If the equipment is likely to come into contact with corrosive and/or other harsh
substances, consult with the relevant technical persons to take suitable precautions to prevent
the detector from being adversely affected, thus ensuring that the type of protection is not
compromised.
Harsh substances: For example, acidic liquids, gases, or solvents that may attack the
windows, metals, seals, or polymeric materials.
Suitable precautions: For example, regular checks as part of routine inspections or
establishing from the material’s datasheet that it is resistant to specific chemicals.
Specific conditions for use
•
The equipment is not intended to be repaired by the user. Repair of this equipment
shall be carried out by the manufacturer per the applicable code of practice.
•
The flame paths are not intended for repair. Contact the manufacturer if the flame
paths are damaged.
•
Consult the manufacturer for a genuine replacement cover and housing to connection
box fasteners. M6x1x18 Hexagonal Socket head fasteners with a minimum of ISO 4762 Grade
A4 Class 80 are acceptable alternatives.
•
One suitably certified stopping plug is supplied with the detector.
•
The external earthing connection consists of a cable lug with an M5x10 stainless steel
screw, the terminals are suitable for connection of a wire of at least 4mm
2
/
12AWG.
•
The internal terminals are suitable for the connection of a wire equal to or greater than
the power input wiring and at a minimum of 1mm
2
/ 17AWG conductor.