F-Guard UV-IR-HD User Manual
76-M-6010-02-02
False Alarm Immunity
The following table shows test results of false alarm immunity for detectors configured to “Extreme”
sensitivity. For each radiation source a distance is listed. This is the minimum tested distance, from which the
detectors did not alarm when exposed to the radiation source (either modulated or non-modulated).
False Stimuli only at Extreme Sensitivity
False Alarm Source
Maximum Distance in ft (m)
Sunlight, Direct, Reflected
No response at any distance
Incandescent frosted glass light, 300W
2 (0.5)
Fluorescent, 70W (3x23.3W)
2 (0.5)
Electric arc
2 (0.5)
Arc welding
10 (3)
Radiation heater, 1850W
2 (0.5)
Quartz lamp (1000W) shielded
2 (0.5)
Quartz lamp (500W) non-shielded
7 (2)
Mercury vapor lamp 160Wx3
2 (0.5)
Car Exhausts
2 (0.5)
Projector led
2 (0.5)
Solenoid bell
2 (0.5)
Soldering iron
2 (0.5)
Electric Drill
2 (0.5)