For more information & technical support:
39
F-Guard UV-IR-HD User Manual
76-M-6010-02-02
F-Guard-UV-IR-F-HD-ASX1, F-Guard-UV-IR-F-HD-ASX2 (Standard
model)
Extreme Sensitivity
Fuel
Size
Distance Feet (m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
98 (30)
3.8
Gasoline
2 x 2 ft
197(60)
4.6
Gasoline
1 x 1 ft
98 (30)
3.7
Methane
32-in Plume
59 (18)
1.6
LPG
32-in Plume
75 (23)
1.2
Diesel
1 x 1 ft
75 (23)
3.8
JP5
1 x 1 ft
75 (23)
3.5
Kerosene
1 x 1 ft
75 (23)
3.4
Methanol
1 x 1 ft
59 (18)
3.7
Ethanol
1 x 1 ft
72 (22)
5.1
Isopropanol
1 x 1 ft
75 (23)
2.8
Polypropylene
1 x 1 ft
49 (15)
2.7
Paper
1 x 1 ft
33 (10)
3.8
Syngas*
32-in Plume
66 (20)
1.3
High Sensitivity
Fuel
Size
Distance Feet (m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
75 (23)
1.5
LPG
32-in Plume
56 (17)
1.6
JP5
1 x 1 ft
56 (17)
3.4
Methanol
1 x 1 ft
43 (13)
1.8