The Gassonic Surveyor has two interface LEDs, which will flash red or green depending on the state of the unit. The LED on the front
of the unit indicates the current mode of the Gassonic Surveyor, and the LED next to the sensor head communicates with the test-
and calibration tool Gassonoc 1701. During service operations with the Gassonic 1701 the communication LED is not visible.
Normal oPeratioN
Front led
communication led
Normal Operation
Green
Off
Voltage Error
Off
On
Internal Trigger level reached
Red
On
Internal Delay time elapsed
Flashing Red
On
Service oPeratioN
Calibration Mode
Flashing Red and Green
Calibration Failure
Flashing Green
Internal Delay time testing
Red
Internal Delay time elapsed
Flashing Red
When using the 4-20 mA and the relay in Error mode
I
min
=600 mW
Unit in alarm. Relay energized
When using the 4-20 mA and the relay in Alarm mode
I
min
=500 mW
Unit in alarm. Relay de-energized
When using only relay output in Alarm mode
I
min
=350 mW
Unit in alarm. Relay de-energized
The unit can operate with a supply voltage of 9 to 28 Vdc. Power consumption patterns below are calculated with a 33%
safety factor, and with the minimum voltage of 9 Vdc.
If the calibration or gain test was faulty the Gassonic 1701 beeps three times and a No response message is displayed
on the screen.
• Check if there is dirt on the optical window between the 1701 and the Gassonic Surveyor.
• Check if there is dirt on the windscreen or on the microphone.
• Replace microphone if nessesary.
11.0 -
GaSSonic SuRVeYoR led inTeRFace
12.0 -
TRouBle ShooTinG
13.0 -
poWeR conSumpTion
Installation and User Guide for Gassonic Surveyor (BB6019-01)
Page 16