Switch the Gassonic 1701 tool on. The ver-
sion number will display briefly. You must now
select the sensor type.
Select
type
Select “Gassonic Surveyor” by pressing the
Down button and then press Enter.
Use default filter 25 kHz by pressing the En-
ter button.
Select test with the Down button.
Select the Gassonic Surveyor calibration by
pressing the Down button, and then press
Enter.
Gassonic
Surveyor
Filter 25 kHz
Select
test
Surveyor
Calibr.
A calibration can be performed at any time. Along with the Gassonic 1701, you will need the magnet-stick to set the
Gassonic Surveyor in calibration mode.
9.0 -
caliBRaTion pRoceduRe
acTion
diSplaY
BuTTon
BuTTon
1
2
3
4
5
Installation and User Guide for Gassonic Surveyor (BB6019-01)
Page 13