![GASSONIC SURVEYOR User Manual Download Page 14](http://html.mh-extra.com/html/gassonic/surveyor/surveyor_user-manual_568584014.webp)
6
7
8
9
10
Activate the test and calibration mode on
the Gassonic Surveyor with the enclosed
magnet-stick. Place the magnet-stick in the
magnet stick notch next to the interface LED
and hold it for more than 3 seconds.
> 3 Sec.
The interface LED will flash green and red to
indicate that the unit is now in test mode.
The test mode will time out after 60 sec of in-
activity and return to normal mode. You may
also return the Gassonic Surveyor to normal
service by placing the magnet stick in the
magnet stick notch again.
Activate the calibration by pressing Enter on
the Gassonic 1701.
Activate
Calibr.
The calibration is carried out automatically,
and will stop when finished. The Gassonic
Surveyor LED turns green.
If the test was faulty the red LED on the Gassonic 1701 flashes
and the message “No response” is displayed on the screen. The
Gassonic Surveyor user LED will flash green for 5 seconds and
then the unit will return to normal operation. Check the chapter
“Trouble shooting” and try calibrating again.
Calibr.
complete
No response
acTion
acTion
diSplaY
diSplaY
BuTTon
Installation and User Guide for Gassonic Surveyor (BB6019-01)
Page 14