10.3
MİNİMUM LOAD EMISSION SETTINGS
11
LPG CONVERSION
Gas conversioned process which is mentioned
below must be issued by authorized GASSERO
services only on Wallcon X-treme 125 and
Wallcon X-treme 150 boilers.
Wallcon X-treme boilers are manufactured to work
with natural gas. Wallcon X-treme 125 and Wallcon
X-treme 150 boilers can be converted into LPG.
If the boiler will be used with LPG, it must be
adjusted by Gassero authorized services according to
the following combustion values and parameters.
42
D
D
WALLCON X-treme 115-125-150
min.
max.
min.
max.
CO
2
emission
%
9,01
11,61
11,09
11,11
Gas consumption
m3 /h
0,53
3,83
0,65
4,41
Gas nozzle
mm
9,00
9,00
G31
Wallcon X-treme
125
Wallcon X-treme
150
LPG EMISSION SETTINGS
Minimum load emission setting is done by
measuring the CO2 value in the flue gas. The
following steps should be followed for this instant
measurement on a boiler operating at minimum
capacity.
HEATING MODE
BUTTON
INFO BUTTON
OK BUTTON
ADJUSTMENT KNOB
To run the boiler at minimum load;
Press and hold Heating Mode button for 3 sec.
«Controller
Stop
Function
On»
will
be
mentioned on the screen
Modulation rate will be displayed in % by
pressing the Info button.
Press
OK
button
and
change
the
modulation rate to %0 by turning the Adjusment
Knob.
Press OK button to apply.
Turn the Minimum Gas Flow Adjustment Screw (D)
clockwise to increase the CO2 value. If you turn it
counterclockwise, the gas flow rate will decrease
and therefore the CO2 value will decrease.