How to check and adjust parameters:
User parameter checking and settings (avail in both ON and OFF state)
In the main interface, press “ function” key for 3 seconds to enter user parameter checking and settings interface;
press “+” or “-” to check each parameter.
Press “ function” to enter current user parameter settings interface, press “ +” or “-” to modify the value, again
press “function” key to return to query status.
Under parameter checking or setting interface, if no operation to the controller within 30 seconds, the
controller will return to main interface automatically. The controller also can back to main interface via pressing
ON/OFF key.
Factory parameter checking and settings (avail in both ON and OFF state)
In the main interface, together press “ ON/OFF” and “ +” keys for 3 seconds to enter factory parameter password
interface. In this interface, press “ time” to switch code digits, press “ +” or “ -“ to modify the value of each digit,
and press “ function” key to input your password, if the password is correct, the controller will enter factory
parameter check interface. ( factory check password: 0814)
In the factory checking interface, press “ function” to enter current factory parameter settings, press “+” or “-“ to
modify the value of the parameter, and press “function” to return to query status.
Under factory parameter query or setting interface, if no operation to the controller within 30 seconds, the
controller will return to main interface automatically. The controller also can return to main interface via
pressing ON/ OFF key.
13.4.
PARAMETER NUMBER AND DESCRIPTION ARE LISTED IN THE FOLLOWING TABLE.
27
13.4.1
USER PARAMETER (AVAILABLE FOR END USERS)
Parameter
code
Parameters descrip tion
Setting range
Defau lt
value
Notes
L0
W ater temp
hysteresis (DHW )
2~18
℃
5
℃
Machine stops when water temp>=set
temp + hysteresis, machine restarts
when water temp<=set temp - hysteresis
L1
Setting water temp (DHW )
20
℃
~Parameter F1
55
℃
Default DHW water temp
L2
W ater temperature
hysteresis(Heating/Cooling)
2
℃~
18
℃
3
℃
Machine stops when water temp>=set
temp + hysteresis, machine restarts
when water temp<=set temp - hysteresis
L3
Setting water temperature of
Heating mode
20
℃~
Parameter F1
50
℃
Default water temp for Heating
L4
Setting water temperature of
Cooling mode
7
℃~
30
℃
12
℃
Default water temp for Cooling
L5
The ambient temperature to
start auxiliary electrical heater
-30
℃~
35
℃
0
℃
W hen ambient temp < set value, turn on
the auxiliary electrical heater
L6
Compressor current protection
value
0
~
40A
100 :23A
200 :13A
300 :10A
380 :13A
450 :15A
550 :13A
630 :15A
If set to 0, means ignore
this value