Installation, Operation and Maintenance Manual
Pressure Regulating Valve – Model Ares N
MI–42
Prepared by
Verified by/ Approved by
CSQ
Date
Revision
Page
José Junior
Vanízio Lizo
Jamerson
24/03/17
02
7 of 21
2.3.8 SET POINT PRESSURES – SSV G-10
SSV – G10
SPRING COLOR
CODE
SETTING RANGE (mbar)
RED
01.52.15
10 – 40
YELLOW
01.52.16
25 – 70
BROWN
01.51.88P
50 – 120
BLUE
01.51.89P
80 – 280
WHITE
01.51.90P
220 – 600
2.3.9 ACCURACY SSV
Accuracy: AG up to 10% according DIN EN 14382
3.0 - OPERATION PRINCIPLE
3.1 ARES N REGULATOR – BASIC INSTALLATION
The pressure regulator series ARES N works by principle of direct spring action against sensor element of outlet
pressure (diaphragm). The consumption variation and consequently change of pressure in the sensor element
(diaphragm) will change diaphragm position and diaphragm lever that acts the shutter shaft, increasing or decreasing the
valve passage in order to keep the outlet pressure constant.
In case of flow absence, the consequently outlet pressure increase is transmitted to the diaphragm resulting in this
upward movement; it will change lever position and shaft that will decrease the gas passage.
With gas consumption the opposite will happen and will open the main valve.