Installation, Operation and Maintenance Manual
Pressure Regulating Valve – Model Ares N
MI–42
Prepared by
Verified by/ Approved by
CSQ
Date
Revision
Page
José Junior
Vanízio Lizo
Jamerson
24/03/17
02
6 of 21
6
49
66
-
-
8
61
-
-
-
NOTE:
1) Informed capacity based on a 20% drop.
2) GN fluid. Density 0.6 KG/m³.
3) Informed pressures in bar and flow rate in m³/h @ 1atm 20ºC.
2.3.5 MAXIMUM WORK PRESSURE
ORIFICE
(mm)
MAXIMUM
PRESSURE (bar)
4
8
6
6
8
3
10
2
The pressure limits given in this manual or in any applicable standard shall not be exceeded under any circumstances,
under risk of damage to the equipment, to the installation safety, and to people involved in the operation.
2.3.6 SET POINT PRESSURES - ARES N
The table below presents the adjustment ranges:
SPRING COLOR
CODE
SETTING RANGE (mbar)
BROWN / ORANGE
01.52.08
5.0 – 15.0
GREY
01.52.07
12.0 - 30.0
ZINCATED
01.52.09
22.0 - 35.0
ORANGE / GREY
01.52.10
30.0 - 75.0
YELLOW
01.52.11
70.0 - 100.0
BROWN
01.52.12
90.0 – 150.0
BLACK
01.52.13
105.0 – 240.0
2.3.7 ACCURACY AND LOCK UP
Accuracy; Lock-up: AC up to 20%; SG up to 20%