Chapter 2
Installation
This chapter provides specific procedures for installing the Magnum DX940, preparing for installation, and
uninstalling the device.
2.1 Preparing for Installation
The DX940 is designed to be installed in standard 19" racks, on a DIN-Rail system, or on a panel.
2.1.1 Tools
Regardless of the mounting system you are using you will need the following tools:
•
Two screw drivers – one Phillips head and one slot.
•
A torque wrench (rated for ten and 32 inch pounds, or 1.1 Nm and 3.6 Nm)
•
A wrench to connect a ground wire from the device chassis to a ground
The instructions in this manual cover only the physical installation. System configuration is handled through
a web-based interface and is described in the MNS-DX Administrator’s Guide.
2.1.2 Site Suitability
Be sure that your installation site meets the following criteria:
Conforms with the temperature and humidity ranges detailed in Table 1-2.
Can meet the power requirements detailed in Table 1-4.
Will remain stable after the addition of the 5 lb. DX940.
Permits at least two inches of space between the DX940 and any other heat
producing device.
2.1.3 Wiring and Grounding Guidelines
The DX940 requires several different types of connectors, cables, and wires. Requirements and
recommendations are listed below:
Grounding
The primary ground stud located on the rear of the chassis
must
be used to connect to an approved ground with a wire
meeting the following criteria:
•
14 AWG (minimum)
•
a maximum of five feet in length
•
terminated on the ground lug side with a #10 ring lug
Facility Power
The facility power cabling attached to the DX940 chassis
must
meet the
following criteria: