Click left touch area until you see ”AddrESS”.

For a stand alone wallbox, recommended address is 002.
This mode will paus the charging process if available current in 
the system is below 6A. 6A is the minimum av EV can charge 
according to standard.
Note: No need to to do any settings in the wallbox webinterface.
Modbus address 002 is the only adress that you can use if you 
dont have any Wifi-module installed in your wallbox
Modbus address 002 is only valid for stand alone wallbox 
installations.
For multiple wallboxes connected in a grid, use address #100. 
DLM settings in the webinterface are required.
Address 100 require an installed wifi-module in the Master 
Wallbox.
Note: When use of Adress 100, the wallbox will not paus the 
charging process if available current is below 6A.
If you want to monitor a 2nd mains cabinets, a 2nd DLM meter 
can be installed in the 2nd mains cabinet. The modbus address 
for the 2nd DLM meter should be 101.
Both 100 and 101 will not paus the charging process if available 
current in the system is below 6A. 
Note: DLM settings are required in the master wallbox 
webinterface.
Modbus address 100 and 101 require an installed wifi-module in 
your master wallbox.

EN

6

Modbus address information

Summary of Contents for GNM3D-RS485

Page 1: ...GARO AB GARO GNM3D RS485 and Box 203 SE 335 25 Gnosj info garo se garo se Manual 380251 GARO GNM3D LP RS485 as DLM meter DLM Dynamic Loadbalancing Meter Installation and Programming Manual EN...

Page 2: ...MODBUS CONNECTION 3 Warnings 3 ELECTRICAL CONNECTION POWER CABLES 4 DLM METER SETTINGS 4 Touch area 4 Modbus address information 6 Set the Modbus Address 7 Set varify the Baudrate 8 Set varify the Par...

Page 3: ...lectrician MODBUS CONNECTION Install the DLM meter in the mains cabinet you want to monitor Use shielded twisted pair cable between the DLM meter and the wallbox Suitable cables CAT5 FTP CAT5e FTP CAT...

Page 4: ...CAL CONNECTION POWER CABLES 1 6 section 2 5 16 mm torque 2 8 Nm 7 12 N section 1 5 mm torque 0 4 Nm DLM METER SETTINGS EN 4 L1 L2 L3 N F N 1 2 3 4 5 6 Touch area F Fuse 315mA if required by local regu...

Page 5: ...Longpress center touch area until you see PASS 1 2 Longpress both left and right touch area to bypass the password The blinking 0 will stop to blink after 2 seconds 5 EN...

Page 6: ...e wallboxes connected in a grid use address 100 DLM settings in the webinterface are required Address 100 require an installed wifi module in the Master Wallbox Note When use of Adress 100 the wallbox...

Page 7: ...ongpress touch area 00 1 starts to blink 2 Click left or right touch area to modify the figure 3 Longpress touch area to change to next figure and repeat step 2 4 When the adress is correct longpress...

Page 8: ...uch area until 9 6 is visible Confirm by longpress touch area 7 Set varify the Parity and stopbit Click left touch area until PArIty is visible Default is no and this is correct If you need to change...

Page 9: ...rm settings 1 Click left touch area until End is visible 2 Longpress center touch area when End is visible and the setting is confirmed 3 The square is blinking when DLM meter have communication with...

Page 10: ......

Reviews: