background image

 5

2.4 Timer Drain Programming Mode

1.

Press the “Drain Interval Program” button (the
“Condensate Draining” LED will start to flash, and
the illuminated LED on the “Dew Point Temperature
Indicator” will identify the factory setting for “Minutes
Between Drain Cycles.”
(See Table 1)

2.

Press and release the “Drain Interval Selector” button
to sequence the “Minutes Between Drain Cycle LED’s”
from left to right until reaching your selection. The
“Red” LED is not used (Reference Table 2 for “Drain
Cycle Intervals”)

3.

To initiate the new setting, press the “Drain Interval
Program” button (this will store the new setting and
exit the program).

4.

Exiting the Program will cause the Timer Drain to
discharge and begin a new cycle.

Note:  Failure to perform step 3 within 25 seconds of
completing step 2 will cause the unit to revert back to the
previous setting.

Note:  In the event of a brief or extended period of
power loss, the unit will retain the existing program
setting and will begin a new cycle once power is reap-
plied. Had drain been ready to drain before the loss of
power, the drain bowl’s capacity would prevent down-
stream flooding. Condensate will drain completely within
a couple of cycles. (Manually pressing the “Push-to-Test”
button would drain bowl immediately)

2.5  Operating check points

Check the following on a periodic basis:

A.   Green power on light is illuminated.
B.   Dewpoint indicator is in green area.
C.   Condensate is discharging from drain.

1.

For minimum inlet air pressures that fall between
column values, the setting for the lower pressure is
recommended. (i.e. select the 100 psi column values
for 124 psi inlet pressure listed in Table 1.)

2.

Where the dryer is consistently operating at less than
maximum capacity, it may be possible to increase the
LED set point to minimize air loss. Discretionary
adjustments to the dryer should only be made on a
hot, humid day when the maximum expected air load
is flowing through the dryer. Failure to do so may
prevent the condensate from draining completely
when operating under peak load conditions.

Table 1  Timed drain illuminated LED Settings

2.2 Start-up

1.

Confirm On/Off Switch is in the “Off” position.

2.

Energize dryer. Green power-on light will illuminate.

2.3 Timer Drain Option

(Only Models with I-Controller Level 2)

Note:  The Timer Drain LED level has been pre-pro-
grammed at the factory for your specific RNC Series
dryer. Programming is based upon a minimum of 100 psi
saturated inlet air pressure and maximum energy effi-
ciency. The drain open time is fixed at one second and a
small amount of air will be exhausted with each cycle.
Generally, no adjustment to the timer is required.

                        If water is present downstream of the
dryer, always verify that any condensate drains installed
upstream of the dryer are draining properly before
attempting to readjust the LED setting.

Inlet Pressure

75

100*

125

150

200

225

RNC25

4

5

5

5

6

6

RNC35

4

4

4

4

5

5

RNC50

3

3

4

4

4

4

RNC75

4

4

4

4

5

5

RNC100

3

3

4

4

4

4

Dr

yer Model

Table 2  LED Legend

* Recommended and pre-programmed factory settings for each RNC Series model dryer.
Assumes CAGI ADF100 inlet conditions with 100

°

F ambient and 10

°

F air-cooled

aftercooler approach temperature.

Minutes

LED

between

Illuminated

Drain Cycles

1

st

1

2

nd

3

3

rd

5

4

th

10

5

th

20

6

th

30

7

th

40

8

th

50

9

th

60

33

°

F......................39

°

F

1

°

C.......................4

°

C

Dew point Temperature

Indicator

Drain
Interval
Selector

Condensate
draining LED
(Flashes in
programming
mode)

Drain Interval
Program

(LED Illuminated indicates

drain cycle time)

Summary of Contents for RNC25

Page 1: ...DELS RNC25 RNC35 RNC50 RNC75 RNC100 CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 4 3 0 MAINTENANCE 6 SIZING 6 ENGINEERING DATA 7 ELECTRICAL SCHEM...

Page 2: ...evidence of loss or damage at time of delivery to you insist that a notation of this loss or damage be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Dama...

Page 3: ...r installation Standard units are designed for indoor installation Contact manufacturer if installing outdoors 1 2 Mounting Mount the dryer on a level solid surface Holes are provided in the dryer bas...

Page 4: ...ranty 1 5 Moisture separator A Separator and Oil Removal Filter where applicable has an internal drain which automatically discharges collected condensate It may be desirable to pipe the condensate fr...

Page 5: ...2 Where the dryer is consistently operating at less than maximum capacity it may be possible to increase the LED set point to minimize air loss Discretionary adjustments to the dryer should only be m...

Page 6: ...d drain mechanism annually To facilitate service maintenance kits are available Please refer to page 11 3 0 Maintenance Sizing Determining dryer capacity at actual operating conditions To determine th...

Page 7: ...29 220 183 350 292 Electrical Nominal Voltages 115 1 60 Max Min Voltage 127 104 127 104 127 104 127 104 127 104 Rated Load Amps 3 4 3 9 5 9 7 4 10 3 Locked Rotor Amps 18 0 22 0 28 0 35 0 48 0 Minimum...

Page 8: ...load TB Terminal Block CAP Start Capacitor SR Start Relay DRN1 Drain Solenoid STD IC2 MTR Compressor DRN2 Drain Solenoid IC2 Oil Coalescing Option FM Fan Motor TC1 Temperature Sensor Optional Notes 1...

Page 9: ...G 18 3 16 18 3 16 18 3 16 20 11 16 20 11 16 H 21 3 16 21 3 16 21 3 16 24 3 16 24 3 16 I 18 1 2 18 1 2 18 1 2 24 24 J 16 1 2 16 1 2 16 1 2 21 13 16 21 13 16 Inlet Outlet Connections 1 2 MPT 1 2 MPT 1 2...

Page 10: ...gh air outlet temperature 2 Refrigeration system not func tioning properly resulting in high air outlet temperature 3 Dryer is running with no load a Power failure b Line disconnect switch open c Blow...

Page 11: ...0 120 5 G4130 120 8 G4130 120 9 G4130 121 11 G4130 121 9 G4130 121 9 G4130 122 10 G4130 122 11 G4130 122 15 Compressor Only G4130 108 34 G4130 108 61 G4130 108 35 G4130 108 38 G4130 108 39 G4130 108 4...

Page 12: ...T OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER REPORT REPAIR OR MODIFY LATENT DEFECTS INHERENT THEREIN THE MANUFACTURER H...

Reviews: