FIELD SERVICE GUIDE

Problems most frequently encountered with refrigerated dry-

ers are water downstream of the dryer and excessive pressure 

drop. Most causes can be identified and remedied by following 

this guide.

  Closed refrigeration systems are potentially dan-

gerous. Work on the refrigeration system must be done only 

by a competent licensed refrigeration mechanic. Do not release 

fluorocarbon refrigerants to the atmosphere. Do not discharge 

liquid refrigerants into floor drains. Refrigerant vapors may accu-

mulate in low places.  Inhalation of high concentrations may be 

fatal. All refrigerants must be recovered per EPA requirements. 

Do not smoke when a refrigeration leak is suspected. Burning 

materials may decompose refrigerants, forming a toxic gas or 

acids that may cause serious injury and property damage.
Before dismantling any part of the dryer or compressed air sys-

tem, completely vent the internal pressure to the atmosphere.

PROBLEM

SYMPTOM

POSSIBLE CAUSE

REMEDY

Water Downstream of 

Dryer

Refrigerant compressor not 

running.

Loss of power to dryer

Check power supply, fuses and/or breakers.  Check 

for loose connections.

Dryer turned off.

Check On/Off switch position. 

Dryer overloaded.

Confirm that inlet flow, inlet temperature and inlet 

pressure are within acceptable range of dryer.

Condenser clogged with debris.

Check/clean condenser.

Fan motor inoperative

Check fan motor operation. Replace if necessary.

Ambient temperature too high.

Verify ambient temperature throughout day.

High pressure switch activated 

(models 200 to 500 only)

Press manual reset button to switch to reset button.

Compressor overheated.

Turn dryer off. Contact local distributor.

Compressor defective.

Turn dryer off. Contact local distributor.

No condensate discharging from 

dryer.

Drain strainer clogged.

Clean drain strainer.

Drain valve inoperative.

Check/rebuild drain valve.

Drain timer or DSM inoperative.

Confirm there is power to the timer or DSM. Replace 

timer or DSM, if necessary.

Drain solenoid inoperative.

Confirm there is power to the coil. Replace coil, if 

necessary.

Condensate discharging from dryer.

Incorrect drain timer setting.

Adjust drain timer - increase open time and/or 

decrease closed time.

Liquid water entering dryer.

Aftercooler drain valve malfunction.

Check, repair aftercooler drain valve.

Excessive Pressure 

Drop Across Dryer

Frozen condensate in evaporator.

Incorrect constant pressure valve 

setting.

Contact local distributor.

Inlet air pressure low.

Upstream restriction in air system.

Check all upstream air system components (valves, 

regulators, etc.)

Dryer undersized.

Excessive compressed air flow.

Resize dryer.

Dew Point Indicator 

Out of Green Zone

Dew Point Indicator Out of Green 

Zone

Dryer overloaded.

Confirm that inlet flow, inlet temperature and inlet 

pressure are within acceptable range of dryer.

Condenser clogged with debris.

Check/clean condenser.

Loose sensor connection.

Confirm gauge or DSM sensor is tightly connected 

to dryer tubing.

Defective gauge, DSM or DSM 

sensor.

Replace gauge, DSM or DSM sensor.

Summary of Contents for RGD Series

Page 1: ...r visit Sales and Service at www gardnerdenverproducts com 7442624 Rev C 08 20 INSTRUCTION MANUAL RGD Series Models RGD75A1 RGD100A1 RGD125A1 RGD150A1 RGD200A4 RGD250A4 RGD300A4 RGD400A4 RGD500A4 REFR...

Page 2: ...ENERAL ARRANGEMENT DRAWINGS Models RGD75A1 through RGD150A1 9 Models RGD200A4 through RGD250A4 10 Models RGD300A4 through RGD500A4 11 ELECTRICAL SCHEMATICS Model RGD75A1 12 Models RGD100A1 through RGD...

Page 3: ...ations for the requirements for breathing quality air RECEIVING MOVING AND UNPACKING A RECEIVING This shipment has been thoroughly checked packed and inspected before leaving our plant It was received...

Page 4: ...the bypass line Compressed air systems commonly require filters to remove compressor oils particulates condensed liquids and other contaminants When an oil removal filter is used it should be install...

Page 5: ...5A1 and RGD150A1 1 7 3 4 10 9 2 8 5 6 Dryer System Monitor Models RGD200A4 RGD250A4 RGD300A4 RGD400A4 and RGD500A4 1 On Off Switch Press the top of the switch I to turn the dryer on Press the bottom o...

Page 6: ...dryer are draining properly before attempting to adjust the timer settings 1 For minimum inlet air pressures that fall between column values the setting for the lower pressure is recommended i e selec...

Page 7: ...nical repairs are to be made or service is performed vent the internal pressure of the dryer to atmospheric pressure Restart the dryer according to the start up instructions Disconnect power supply an...

Page 8: ...e performed 1 Inspect internal parts of valve body clean or replace as required NOTE Replace solenoid valve if component damage is observed 2 Remove debris from valve body 3 Wipe solenoid core compone...

Page 9: ...e if necessary Ambient temperature too high Verify ambient temperature throughout day High pressure switch activated models 200 to 500 only Press manual reset button to switch to reset button Compress...

Page 10: ...5 26 5 31 7 40 6 38 8 44 1 63 5 1 Rated Flow Capacity Conditions for rating dryers are in accordance with ISO 7183 Option A2 Compressed air at dryer inlet 100 psig 6 7 barg and 100 F 38 C ambient air...

Page 11: ...4 28 362 6 12 76 324 21 70 551 2 23 67 601 2 2 16 55 4 38 111 2 2 02 51 2 1 18 30 1 18 30 1 100 2 02 51 2 3 79 96 2 1 96 50 19 26 489 2 2 44 62 32 33 821 2 21 26 540 31 15 791 2 1 18 30 14 28 362 6 12...

Page 12: ...G H I MODEL DIMENSIONS INCHES MM CONNECTIONS INCHES NPT A B C D E F G H I J K L M N O P Q R 200 2 65 67 2 7 13 181 2 1 96 50 24 38 619 2 3 62 92 36 66 931 2 28 74 730 35 48 901 2 1 18 30 19 39 492 6 1...

Page 13: ...1 96 50 25 56 649 2 4 41 112 43 75 1111 2 35 83 910 42 57 1081 2 1 18 30 19 39 492 6 17 87 454 29 97 761 2 31 94 811 2 2 36 60 5 95 151 2 3 20 81 2 1 58 40 1 58 30 2 500 2 65 67 2 7 13 181 2 1 96 50...

Page 14: ...valve timer Customer s installation Ref Compressor M1 C S M R S2 CR SOL1 Electric drain SK1 Spark Killer Resistance 120 Capacitor 0 1uF M1 Ref Compressor GL1 S1 L N S0 S3 L1 N1 T1 SOL1 M2 SK1 2 3 LEG...

Page 15: ...rain valve timer SOL1 Electric drain SK1 Spark Killer Resistance 120 Capacitor 0 1uF Customer s installation Ref Compressor M1 CS C S M R S2 CR CR Running capacitor GL1 S1 L N S0 M2 S3 L1 N1 T1 SOL1 S...

Page 16: ...0 M2 L1 N1 T1 SOL1 SK1 S2 2 1 S3 S4 N1 8 7 LEGEND CR Running Capacitor M1 Ref Compressor M2 Fan Motor GL1 Green Lamp CH Crankcase Heater S1 Switch on off S2 Overload Protector S3 Fan Pressure Switch S...

Page 17: ...GL1 S1 MC1 S4 S3 T2 R2 MC2 TH1 T1 R1 M2 M1 SK1 12 11 COM COMP COMP S1 A2 FG A1 A2 R2 T2 R2 8 FG RCOM RB RA 2 1 8 7 13 LEGEND M1 Ref Compressor M2 Fan Motor MC1 Magnetic Contactor MC2 Magnetic Contact...

Page 18: ...S4 S3 T2 R2 MC2 TH1 T1 R1 M2 M1 SK1 12 11 COM COMP COMP S1 A2 FG A1 A2 R2 T2 R2 8 FG RCOM RB RA 2 1 8 7 13 LEGEND M1 Ref Compressor M2 Fan Motor MC1 Magnetic Contactor MC2 Magnetic Contactor S1 Switch...

Page 19: ...MC1 Magnetic Contactor MC2 Magnetic Contactor Ref Compressor Fan Motor TEMP SENSOR Drain valve TB1 TB1 Terminal Block for Main Power Customer s installation L3 L1 E L2 GL1 S1 MC1 S4 S3 T2 R2 MC2 TH1 T...

Page 20: ...VALVE TEMP SENSOR FOR PANEL DISPLAY TI SCHRADER VALVE REF AIR S WETTED AIR INLET DRIED AIR OUTLET AIR AIR MOISTURE SEPARATOR INTEGRATED STRAINER AUTO DRAIN VALVE DRAIN OUTLET TIMED ELECTRIC BALL VALVE...

Page 21: ...RGD250A4 RGD300A4 RGD400A4 RGD500A4 1 Refrigerant Compressor G3161251 G3161251 G3093041 G3137014 G3137014 2 Condenser G7433669 G7478057 G7433670 G7433671 G7433672 3 Fan Blades G3041958 4 Fan Motor G7...

Page 22: ...n valve prefilter element afterfilter element filter drain 2 RGDMKF9 RGDMKF9 RGDMKF10 RGDMKF23 Model Kit Components RGD200A4 RGD250A4 RGD300A4 RGD400A4 RGD500A4 Standard Kit Drain valve G7477982 G7477...

Page 23: ......

Page 24: ...rranty claim once submitted Unauthorized service and use of unauthorized or pirated parts voids the warranty and any resulting charges or subsequent claim will not be paid Products repaired or replace...

Reviews: