background image

2

Compressor

Oil Removal

Filter

Aftercooler

Automatic Drain

Dryer

Separator

Receiver

TYPICAL COMPRESSED AIR SYSTEM

INSTALLATION

Ambient Air Temperature

Locate the dryer indoors where the ambient air temperature will 

be between 37°F and 110°F. Intermittent operation at ambient 

temperatures up to 113°F will not damage the dryer but may 

result in a higher dew point or dryer shutdown due to high 

refrigerant discharge pressure (see Field Service Guide).
Do not operate air-cooled dryers at ambient air temperatures 

below 40°F. Such operation may result in low suction pressure, 

causing freeze-up.

Location and Clearance

Mount the dryer on a level base. If the base vibrates, bolt the 

unit down using vibration dampeners. Allow at least 24 inches 

clearance on the sides and the front of the dryer for cooling 

airflow and for service access.

System Arrangement

Liquid water in the inlet air will adversely affect the performance 

of the dryer. Install the dryer downstream of an aftercooler or 

separator so that the temperature of the dryer inlet air does not 

exceed 120°F and the inlet air does not contain any liquid water.
If the compressed airflow is relatively constant and does not 

exceed the dryer flow rating, it is recommended that the dryer 

be located downstream of the receiver tank. If the nature of the 

application is such that the air demand regularly exceeds the 

dryer flow rating, it is recommended that the dryer be located 

upstream of the receiver.
For safety and convenience, install inlet and outlet shutoff valves 

and depressurization valves. These valves allow the dryer to be 

isolated and depressurized for servicing. Bypass piping may 

be installed around the dryer for uninterrupted airflow when 

the dryer is serviced. If the compressed air operation cannot 

tolerate undried air for short periods, install a second dryer in 

the bypass line.
Compressed air systems commonly require filters to remove 

compressor oils, particulates, condensed liquids and other 

contaminants. When an oil-removal filter is used, it should be 

installed downstream of the refrigerated dryer. At this location, 

the life of the replaceable filter element is prolonged since 

some of the entrained oil is removed by the dryer and drained 

through the separator.

Piping and Connections

Piping must be furnished by the user unless otherwise speci-

fied. Connections and fittings must be rated for the maximum 

operating pressure given on the dryer data plate and must be 

in accordance with applicable codes. Support all piping; do not 

allow the weight of any piping to stress the dryer or filter con-

nections. Inlet and outlet shutoff valves and a valved bypass 

valve are recommended. Piping should be at least the size of 

the inlet and outlet connections to minimize pressure drop in 

the air system. See Engineering Data section for dryer inlet and 

outlet connections.

Removing Condensate

Condensate must be drained from the dryer to prevent re-

entrainment. The dryers are equipped with automatic drain 

valves and internal drain hoses up to the drain connections on 

the dryer cabinets. The user must install a separate discharge 

line at the drain connection to carry off condensate to an envi-

ronmentally approved condensate collection/disposal system. 

Piping or copper tubing 1/2 inch or larger is recommended 

for condensate discharge lines. Install the drain lines so that 

condensate can be seen as it drains.

Electrical Connections

The dryers are constructed according to NEMA Type 1 electrical 

standards. Field wiring must comply with local and national fire, 

safety and electrical codes. Installation must be in accordance 

with the National Electrical Code. Confirm that your line voltage 

is the same as the voltage listed on the dryer data plate. Refer 

to Figure 1 for electrical schematics.

 Operation of dryers with improper line volt-

age constitutes abuse and could affect the dryer war-

ranty.

Summary of Contents for RGD Series

Page 1: ...r visit Sales and Service at www gardnerdenverproducts com 7442624 Rev C 08 20 INSTRUCTION MANUAL RGD Series Models RGD75A1 RGD100A1 RGD125A1 RGD150A1 RGD200A4 RGD250A4 RGD300A4 RGD400A4 RGD500A4 REFR...

Page 2: ...ENERAL ARRANGEMENT DRAWINGS Models RGD75A1 through RGD150A1 9 Models RGD200A4 through RGD250A4 10 Models RGD300A4 through RGD500A4 11 ELECTRICAL SCHEMATICS Model RGD75A1 12 Models RGD100A1 through RGD...

Page 3: ...ations for the requirements for breathing quality air RECEIVING MOVING AND UNPACKING A RECEIVING This shipment has been thoroughly checked packed and inspected before leaving our plant It was received...

Page 4: ...the bypass line Compressed air systems commonly require filters to remove compressor oils particulates condensed liquids and other contaminants When an oil removal filter is used it should be install...

Page 5: ...5A1 and RGD150A1 1 7 3 4 10 9 2 8 5 6 Dryer System Monitor Models RGD200A4 RGD250A4 RGD300A4 RGD400A4 and RGD500A4 1 On Off Switch Press the top of the switch I to turn the dryer on Press the bottom o...

Page 6: ...dryer are draining properly before attempting to adjust the timer settings 1 For minimum inlet air pressures that fall between column values the setting for the lower pressure is recommended i e selec...

Page 7: ...nical repairs are to be made or service is performed vent the internal pressure of the dryer to atmospheric pressure Restart the dryer according to the start up instructions Disconnect power supply an...

Page 8: ...e performed 1 Inspect internal parts of valve body clean or replace as required NOTE Replace solenoid valve if component damage is observed 2 Remove debris from valve body 3 Wipe solenoid core compone...

Page 9: ...e if necessary Ambient temperature too high Verify ambient temperature throughout day High pressure switch activated models 200 to 500 only Press manual reset button to switch to reset button Compress...

Page 10: ...5 26 5 31 7 40 6 38 8 44 1 63 5 1 Rated Flow Capacity Conditions for rating dryers are in accordance with ISO 7183 Option A2 Compressed air at dryer inlet 100 psig 6 7 barg and 100 F 38 C ambient air...

Page 11: ...4 28 362 6 12 76 324 21 70 551 2 23 67 601 2 2 16 55 4 38 111 2 2 02 51 2 1 18 30 1 18 30 1 100 2 02 51 2 3 79 96 2 1 96 50 19 26 489 2 2 44 62 32 33 821 2 21 26 540 31 15 791 2 1 18 30 14 28 362 6 12...

Page 12: ...G H I MODEL DIMENSIONS INCHES MM CONNECTIONS INCHES NPT A B C D E F G H I J K L M N O P Q R 200 2 65 67 2 7 13 181 2 1 96 50 24 38 619 2 3 62 92 36 66 931 2 28 74 730 35 48 901 2 1 18 30 19 39 492 6 1...

Page 13: ...1 96 50 25 56 649 2 4 41 112 43 75 1111 2 35 83 910 42 57 1081 2 1 18 30 19 39 492 6 17 87 454 29 97 761 2 31 94 811 2 2 36 60 5 95 151 2 3 20 81 2 1 58 40 1 58 30 2 500 2 65 67 2 7 13 181 2 1 96 50...

Page 14: ...valve timer Customer s installation Ref Compressor M1 C S M R S2 CR SOL1 Electric drain SK1 Spark Killer Resistance 120 Capacitor 0 1uF M1 Ref Compressor GL1 S1 L N S0 S3 L1 N1 T1 SOL1 M2 SK1 2 3 LEG...

Page 15: ...rain valve timer SOL1 Electric drain SK1 Spark Killer Resistance 120 Capacitor 0 1uF Customer s installation Ref Compressor M1 CS C S M R S2 CR CR Running capacitor GL1 S1 L N S0 M2 S3 L1 N1 T1 SOL1 S...

Page 16: ...0 M2 L1 N1 T1 SOL1 SK1 S2 2 1 S3 S4 N1 8 7 LEGEND CR Running Capacitor M1 Ref Compressor M2 Fan Motor GL1 Green Lamp CH Crankcase Heater S1 Switch on off S2 Overload Protector S3 Fan Pressure Switch S...

Page 17: ...GL1 S1 MC1 S4 S3 T2 R2 MC2 TH1 T1 R1 M2 M1 SK1 12 11 COM COMP COMP S1 A2 FG A1 A2 R2 T2 R2 8 FG RCOM RB RA 2 1 8 7 13 LEGEND M1 Ref Compressor M2 Fan Motor MC1 Magnetic Contactor MC2 Magnetic Contact...

Page 18: ...S4 S3 T2 R2 MC2 TH1 T1 R1 M2 M1 SK1 12 11 COM COMP COMP S1 A2 FG A1 A2 R2 T2 R2 8 FG RCOM RB RA 2 1 8 7 13 LEGEND M1 Ref Compressor M2 Fan Motor MC1 Magnetic Contactor MC2 Magnetic Contactor S1 Switch...

Page 19: ...MC1 Magnetic Contactor MC2 Magnetic Contactor Ref Compressor Fan Motor TEMP SENSOR Drain valve TB1 TB1 Terminal Block for Main Power Customer s installation L3 L1 E L2 GL1 S1 MC1 S4 S3 T2 R2 MC2 TH1 T...

Page 20: ...VALVE TEMP SENSOR FOR PANEL DISPLAY TI SCHRADER VALVE REF AIR S WETTED AIR INLET DRIED AIR OUTLET AIR AIR MOISTURE SEPARATOR INTEGRATED STRAINER AUTO DRAIN VALVE DRAIN OUTLET TIMED ELECTRIC BALL VALVE...

Page 21: ...RGD250A4 RGD300A4 RGD400A4 RGD500A4 1 Refrigerant Compressor G3161251 G3161251 G3093041 G3137014 G3137014 2 Condenser G7433669 G7478057 G7433670 G7433671 G7433672 3 Fan Blades G3041958 4 Fan Motor G7...

Page 22: ...n valve prefilter element afterfilter element filter drain 2 RGDMKF9 RGDMKF9 RGDMKF10 RGDMKF23 Model Kit Components RGD200A4 RGD250A4 RGD300A4 RGD400A4 RGD500A4 Standard Kit Drain valve G7477982 G7477...

Page 23: ......

Page 24: ...rranty claim once submitted Unauthorized service and use of unauthorized or pirated parts voids the warranty and any resulting charges or subsequent claim will not be paid Products repaired or replace...

Reviews: