background image

4

Automatic Drain Valve 

All models are equipped with an electronic drain valve that au-

tomatically discharges condensate from the dryer. Drain valve 

operation is controlled by a drain valve timer. The drain opening 

can be set from 0.5 seconds to 9 seconds. The drain cycle can 

be set from 0.5 minutes to 15 minutes.
Models 75 through 150 have the timer mounted directly on 

the drain valve.  
For models 200 through 500, drain valve adjustments are made 

on the Dryer System Monitor:
1.  Press the Selection (4) and Enter (5) buttons at the same 

time for 3 seconds, the On Time Setting Mode LED (3) will 

start to blink, and the illuminated LED on the Dew Point 

Temperature Indicator LED (2) will identify the factory set-

ting for "On Time". (See table)

2.  Press and release the Selection button (4) to sequence from 

left to right until reaching your selection. The red LED is 

not used.

3.  To store the "On Time", press the Enter button (5) and set 

the "Off Time" using step 2.

4.  To store the "Off Time", press the Enter button (5) again.
5.  Exiting the Program will cause the Timer Drain to discharge 

and begin a new cycle.

NOTE:

 Failure to perform step 3 within 10 seconds of complet-

ing step 2 will cause the unit to revert back to the previous 

setting.

LED (2)

Position

1st

2nd

3rd

4th

5th

6th

7th

8th

9th

On

Time

(sec)

1

2

3

4

5

6

7

8

Continuous

(Drain Trap 

Option)

Off

Time

(min)

0.5

1

2

3

5

7

9

10

15

Electronic Drain Valve Adjustment 

The automatic drain valve has been pre-programmed at the 

factory for your specific RGD Series dryer. Programming is 

based upon a minimum of 100 psi saturated inlet air pressure 

and maximum energy efficiency. Generally no adjustment to 

the timer is necessary.

CAUTION:

 If water is present downstream of the dryer, always 

verify that and condensate drains installed upstream of the 

dryer are draining properly before attempting to adjust the 

timer settings.
1.  For minimum inlet air pressures that fall between column 

values the setting for the lower pressure is recommended. 

(i.e. select the 100 psi column values for 124 psi inlet pres-

sure.)

2.  Where the dryer is consistently operating at less than 

maximum capacity, it may be possible to alter the timer set 

points to minimize air loss. Discretionary adjustments to the 

dryer should only be made on a hot, humid day when the 

maximum expected air load is flowing through the dryer. 

Failure to do so may prevent the condensate from draining 

completely when operating under peak load conditions.

Dryer Model

Inlet Pressure (psig)

75

100*

125

150

200

225

On

Off

On

Off

On

Off

On

Off

On

Off

On

Off

(sec) (min) (sec) (min) (sec) (min) (sec) (min) (sec) (min) (sec) (min)

RGD75A1

2

3

2

3

2

5

2

6

2

9

2

9

RGD100A1

2

2

2

2

2

4

2

6

2

7

2

9

RGD125A1

2

2

2

2

2

3

2

5

2

6

2

7

RGD150A1

2

1

2

2

2

3

2

4

2

6

2

7

RGD200A4

2

5

2

5

2

7

2

9

2

9

2

9

RGD250A4

2

4

2

4

2

6

2

9

2

9

2

9

RGD300A4

2

3

2

3

2

5

2

7

2

9

2

9

RGD400A4

2

2

2

2

2

4

2

6

2

9

2

9

RGD500A4

2

2

2

2

2

4

2

5

2

7

2

9

* Recommended and pre-programmed factory settings for each RGD Series 

model dryer.

Assumes dryer operates at ISO 7183 (Option A2) conditions: 100°F inlet air tem-

perature, 100 psig operating pressure, 100°F ambient air temperature and 10°F 

air-cooled after-cooler approach temperature.

3

4

2

1

5

Drain Timer

(Models RGD75A1, RGD100A1, RGD125A1 and RGD150A1)

1.  Adjustment knob for the drain valve open time. The 

values on the dial correspond to the time in seconds 

that the valve is open in each drain cycle.

2.  Adjustment knob for the drain valve closed time. The 

values on the dial correspond to the time in minutes 

that the valve is closed in each drain cycle.

3.  LED to indicate when the drain valve is open.
4.  Drain test button. When the button is pressed, the 

drain valve opens for the time corresponding to the 

setting on item 1.

5.  LED to indicate when the drain valve is closed.

Summary of Contents for RGD Series

Page 1: ...r visit Sales and Service at www gardnerdenverproducts com 7442624 Rev C 08 20 INSTRUCTION MANUAL RGD Series Models RGD75A1 RGD100A1 RGD125A1 RGD150A1 RGD200A4 RGD250A4 RGD300A4 RGD400A4 RGD500A4 REFR...

Page 2: ...ENERAL ARRANGEMENT DRAWINGS Models RGD75A1 through RGD150A1 9 Models RGD200A4 through RGD250A4 10 Models RGD300A4 through RGD500A4 11 ELECTRICAL SCHEMATICS Model RGD75A1 12 Models RGD100A1 through RGD...

Page 3: ...ations for the requirements for breathing quality air RECEIVING MOVING AND UNPACKING A RECEIVING This shipment has been thoroughly checked packed and inspected before leaving our plant It was received...

Page 4: ...the bypass line Compressed air systems commonly require filters to remove compressor oils particulates condensed liquids and other contaminants When an oil removal filter is used it should be install...

Page 5: ...5A1 and RGD150A1 1 7 3 4 10 9 2 8 5 6 Dryer System Monitor Models RGD200A4 RGD250A4 RGD300A4 RGD400A4 and RGD500A4 1 On Off Switch Press the top of the switch I to turn the dryer on Press the bottom o...

Page 6: ...dryer are draining properly before attempting to adjust the timer settings 1 For minimum inlet air pressures that fall between column values the setting for the lower pressure is recommended i e selec...

Page 7: ...nical repairs are to be made or service is performed vent the internal pressure of the dryer to atmospheric pressure Restart the dryer according to the start up instructions Disconnect power supply an...

Page 8: ...e performed 1 Inspect internal parts of valve body clean or replace as required NOTE Replace solenoid valve if component damage is observed 2 Remove debris from valve body 3 Wipe solenoid core compone...

Page 9: ...e if necessary Ambient temperature too high Verify ambient temperature throughout day High pressure switch activated models 200 to 500 only Press manual reset button to switch to reset button Compress...

Page 10: ...5 26 5 31 7 40 6 38 8 44 1 63 5 1 Rated Flow Capacity Conditions for rating dryers are in accordance with ISO 7183 Option A2 Compressed air at dryer inlet 100 psig 6 7 barg and 100 F 38 C ambient air...

Page 11: ...4 28 362 6 12 76 324 21 70 551 2 23 67 601 2 2 16 55 4 38 111 2 2 02 51 2 1 18 30 1 18 30 1 100 2 02 51 2 3 79 96 2 1 96 50 19 26 489 2 2 44 62 32 33 821 2 21 26 540 31 15 791 2 1 18 30 14 28 362 6 12...

Page 12: ...G H I MODEL DIMENSIONS INCHES MM CONNECTIONS INCHES NPT A B C D E F G H I J K L M N O P Q R 200 2 65 67 2 7 13 181 2 1 96 50 24 38 619 2 3 62 92 36 66 931 2 28 74 730 35 48 901 2 1 18 30 19 39 492 6 1...

Page 13: ...1 96 50 25 56 649 2 4 41 112 43 75 1111 2 35 83 910 42 57 1081 2 1 18 30 19 39 492 6 17 87 454 29 97 761 2 31 94 811 2 2 36 60 5 95 151 2 3 20 81 2 1 58 40 1 58 30 2 500 2 65 67 2 7 13 181 2 1 96 50...

Page 14: ...valve timer Customer s installation Ref Compressor M1 C S M R S2 CR SOL1 Electric drain SK1 Spark Killer Resistance 120 Capacitor 0 1uF M1 Ref Compressor GL1 S1 L N S0 S3 L1 N1 T1 SOL1 M2 SK1 2 3 LEG...

Page 15: ...rain valve timer SOL1 Electric drain SK1 Spark Killer Resistance 120 Capacitor 0 1uF Customer s installation Ref Compressor M1 CS C S M R S2 CR CR Running capacitor GL1 S1 L N S0 M2 S3 L1 N1 T1 SOL1 S...

Page 16: ...0 M2 L1 N1 T1 SOL1 SK1 S2 2 1 S3 S4 N1 8 7 LEGEND CR Running Capacitor M1 Ref Compressor M2 Fan Motor GL1 Green Lamp CH Crankcase Heater S1 Switch on off S2 Overload Protector S3 Fan Pressure Switch S...

Page 17: ...GL1 S1 MC1 S4 S3 T2 R2 MC2 TH1 T1 R1 M2 M1 SK1 12 11 COM COMP COMP S1 A2 FG A1 A2 R2 T2 R2 8 FG RCOM RB RA 2 1 8 7 13 LEGEND M1 Ref Compressor M2 Fan Motor MC1 Magnetic Contactor MC2 Magnetic Contact...

Page 18: ...S4 S3 T2 R2 MC2 TH1 T1 R1 M2 M1 SK1 12 11 COM COMP COMP S1 A2 FG A1 A2 R2 T2 R2 8 FG RCOM RB RA 2 1 8 7 13 LEGEND M1 Ref Compressor M2 Fan Motor MC1 Magnetic Contactor MC2 Magnetic Contactor S1 Switch...

Page 19: ...MC1 Magnetic Contactor MC2 Magnetic Contactor Ref Compressor Fan Motor TEMP SENSOR Drain valve TB1 TB1 Terminal Block for Main Power Customer s installation L3 L1 E L2 GL1 S1 MC1 S4 S3 T2 R2 MC2 TH1 T...

Page 20: ...VALVE TEMP SENSOR FOR PANEL DISPLAY TI SCHRADER VALVE REF AIR S WETTED AIR INLET DRIED AIR OUTLET AIR AIR MOISTURE SEPARATOR INTEGRATED STRAINER AUTO DRAIN VALVE DRAIN OUTLET TIMED ELECTRIC BALL VALVE...

Page 21: ...RGD250A4 RGD300A4 RGD400A4 RGD500A4 1 Refrigerant Compressor G3161251 G3161251 G3093041 G3137014 G3137014 2 Condenser G7433669 G7478057 G7433670 G7433671 G7433672 3 Fan Blades G3041958 4 Fan Motor G7...

Page 22: ...n valve prefilter element afterfilter element filter drain 2 RGDMKF9 RGDMKF9 RGDMKF10 RGDMKF23 Model Kit Components RGD200A4 RGD250A4 RGD300A4 RGD400A4 RGD500A4 Standard Kit Drain valve G7477982 G7477...

Page 23: ......

Page 24: ...rranty claim once submitted Unauthorized service and use of unauthorized or pirated parts voids the warranty and any resulting charges or subsequent claim will not be paid Products repaired or replace...

Reviews: