13-11-607 Page 24
4.
This step is only encountered if the AUTO RESTART function was set to ON in the previous step. In
the top line, “
RESTART DELAY
” is displayed. The bottom line will indicate a time between 5 and 60
seconds. It is factory set at 10 seconds. This is the amount of delay introduced before restarting
after power has been restored. Set it as desired to allow for power to stabilize before starting
compressors.
5.
The display now reads “
JOG MOTOR?
” and indicates the amount of time to energize the starter.
Adjust with the [+] or [-] key to the smallest value needed to bump the motor and check rotation. 0.1
o 0.2 seconds is normally adequate for factory-furnished full-voltage starters; Wye-Delta or remote
starters may require a little more time. Set back to zero to proceed to the next step.
6.
In the top line, “
AUX SD MESSAGE
” is displayed. The bottom line will display the message which
will appear if power is removed from the shutdown input on the optional expansion board. Select the
most appropriate message for user-furnished shutdown devices, and press [ENTER] to proceed.
7.
This completes the unit setup adjustments. The controller will return to the main adjustments menu.
OTHER CONTROL FEATURES
Auto restart after power failure - The AUTO SENTRY W controller normally displays “SHUTDOWN -
POWER FAILURE” after power has been interrupted and restored. Press the [STOP/RESET] key and
select an operating mode to restart the compressor.
If programmed for automatic restart, the controller pauses and begins counting down when power is
restored. This time is adjustable in the programming steps noted above. This must be at least several
seconds, but may be set longer to allow other plant loads to start up first. After the countdown is
complete, the controller resumes the mode of operation prior to the power interruption.
When auto restart is enabled, the green power indicator will blink whenever power is on. With auto
restart disabled, the power indicator lights steadily while power is on.
SEQUENCING COMPRESSORS WITH THE AUTO SENTRY W
An accessory expansion board, part number 301EWC1173, is required in each controller for sequencing
operation. This is included with any package ordered with wye-delta starters, and may be ordered
separately and installed on other packages. Refer to expansion board connection instructions later in this
section.
Sequencing compressors with the AUTO SENTRY W controller is as simple as plugging in a telephone to
a wall jack. The only item required to make the system functional is a standard telephone cable identical
to cables that connect nearly every telephone to its wall jack. One less cable than the number of
compressors to be sequenced is required. For example, to sequence four compressors, three cables are
required. A kit, 200EAP752, is available which contains all material needed to sequence up to five
compressors. This kit contains 500 feet of cable, eight modular connectors, and a crimping tool to install
the connectors.
In spite of its inherent installation simplicity, the sequencing function of a multi-compressor AUTO
SENTRY W system provides all the necessary features for maintaining pressure over a wide range of
plant demands.
Summary of Contents for PUREAIR EWC99C
Page 7: ...13 11 607 Page 2 Figure 1 2 PACKAGE ILLUSTRATION 307EWC797 B Ref Drawing...
Page 8: ...13 11 607 Page 3 Figure 1 3 AIR WATER SCHEMATIC 308EWC797 F Ref Drawing...
Page 25: ...13 11 607 Page 20 Figure 4 2 FLOW CHART FOR SETUP PROGRAMMING 300EWC1255 Ref Drawing...
Page 38: ...13 11 607 Page 33 Figure 4 4 WIRING DIAGRAM FULL VOLTAGE 305EWC546 B Ref Drawing Page 1 of 2...
Page 39: ...13 11 607 Page 34 305EWC546 B Ref Drawing Page 2 of 2...
Page 41: ...13 11 607 Page 36 306EWC546 B Ref Drawing Page 2 of 2...