13-17-621 Page 62
Figure 79: Remote Halt Mode
Timed
mode means the compressor will stop after the unload, blowdown, and automatic stop timers have
expired upon receiving a remote halt signal. The compressor will act as if the pressure exceeded the unload
set point. If the remote halt signal is removed at any point the compressor will re-load, as long as the
pressure is not above the unload pressure set point.
Immediate
mode means the compressor will unload, blowdown, and stop immediately upon receiving a
remote halt signal. This stopping process is essentially the same as if the stop button has been pressed on
the controller.
Disabled
mode is used when there are no remote halt signals programmed to a digital input or when this
function needs to be switched off for any reason. Control will continue locally at the machine controller in
this mode.
4.2.6 Timer Start Enable
Timer Start Enable
allows the user to
enable
or
disable
the starting and stopping of the machine under
timer control. If currently shown as
Off
then pressing it again will toggle it to
O
n and Vice-Versa. Refer
Figure 80 below.
When the
Timer Start Enable
is turned on the compressor will start and stop based on the schedule set
under the timer control settings page. If this is disabled then the compressor will continue to run as
normal regardless of the schedule.
Figure 80: Timer Start Enable